Lucent Technologies 555-233-115 Server User Manual


 
DEFINITY Enterprise Communications Server Release 8.2
Upgrades and Additions for R8r
555-233-115
Issue 1
April 2000
Multicarrier G2 Universal Module to R8r EPN
5-28Standard Reliability
5
For Either 1 or 2 Collocated Expansion Port Networks
1. Behind control carrier A of PPN cabinet 1 (see Figure 5-5, Figure 5-6, and
Figure 5-7
):
Install a lightwave transceiver on the cable connector at slot 1A01.
NOTE:
Attenuators may be required for single mode fiber using a
300A Lightwave Transceiver
Connect 1 end of the fiber optic cable to the lightwave transceiver,
just installed, at slot 1A01.
Carefully attach the fiber optic cable (with cable ties) to the wall of
the cable tray at the built-in cable tie positions.
2. Behind control carrier A of EPN cabinet 2:
Install a lightwave transceiver on cable connector at slot 2A01.
NOTE:
Attenuators may be required for single mode fiber using a
300A Lightwave Transceiver
Connect the other end of the fiber optic cable to the lightwave
transceiver, just installed, at slot 2A01.
Carefully attach the fiber optic cable (with cable ties) to the wall of
the cable tray at the built-in cable tie positions.
At the top of the cabinet, coil up the surplus fiber optic cable and
attach it to the wall of the cable tray.