Raritan Computer EMX2-111 Network Card User Manual


 
Chapter 10: Using the Command Line Interface
285
config:#
sensor externalsensor <n> <sensor type> upperCritical <option>
Variables:
<n> is the ID number of the environmental sensor that you want to
configure. The ID number is assigned and shown in the EMX web
interface. It is an integer between 1 and 16.
<sensor type> is one of these sensor types: temperature, humidity,
airPressure or air Flow.
Note: If the specified sensor type does not match the type of the
specified environmental sensor, this error message appears:
"Specified sensor type 'XXX' does not match the sensor's type
(<sensortype>)," where XXX is the specified sensor type, and
<sensortype> is the correct sensor type.
<option> is one of the options: enable, disable or a numeric value.
Option
Description
enable
Enables the upper critical threshold for the
specified environmental sensor.
disable
Disables the upper critical threshold for the
specified environmental sensor.
A numeric
value
Sets a value for the upper critical threshold of the
specified environmental sensor and enables this
threshold at the same time.
Example
The following command sets the Upper Critical threshold of the
environmental "temperature" sensor with the ID number 2 to 40 degrees
Celsius. It also enables the upper critical threshold if this threshold has
not been enabled yet.
config:#
sensor externalsensor 2 temperature upperCritical 40
Setting the Sensor's Upper Warning Threshold
This command syntax configures the Upper Warning threshold of a
numeric environmental sensor.