Raritan Computer EMX2-111 Network Card User Manual


 
Chapter 10: Using the Command Line Interface
288
config:#
sensor externalsensor <n> <sensor type> lowerWarning <option>
Variables:
<n> is the ID number of the environmental sensor that you want to
configure. The ID number is assigned and shown in the EMX web
interface. It is an integer between 1 and 16.
<sensor type> is one of these sensor types: temperature, humidity,
airPressure or air Flow.
Note: If the specified sensor type does not match the type of the
specified environmental sensor, this error message appears:
"Specified sensor type 'XXX' does not match the sensor's type
(<sensortype>)," where XXX is the specified sensor type, and
<sensortype> is the correct sensor type.
<option> is one of the options: enable, disable or a numeric value.
Option
Description
enable
Enables the lower warning threshold for the
specified environmental sensor.
disable
Disables the lower warning threshold for the
specified environmental sensor.
A numeric
value
Sets a value for the lower warning threshold of
the specified environmental sensor and enables
this threshold at the same time.
Example
The following command disables the Lower Warning threshold of the
environmental "humidity" sensor with the ID number 3.
config:#
sensor externalsensor 3 humidity lowerWarning disable
Setting the Sensor's Deassertion Hysteresis
This command syntax configures the deassertion hysteresis value of a
numeric environmental sensor.