MAP 0100: Power Distribution Analysis
3-29
Diagnostics
3
Is remote fault isolation being performed at the EFC Server?
YES NO
Remote fault isolation is being performed through the
SANpilot interface. Go to step 20.
4
Does inspection of a power supply indicate a failure (green LED
extinguished)?
NO YES
Go to step 6.
5
Does a blinking red and yellow diamond (failed FRU indicator) appear
to overlay a power supply graphic at the EFC Server Hardware View?
YES NO
Go to step 11.
6
A redundant power supply is disconnected from facility AC power, not
properly installed, or has failed.
Verify the indicated power supply is connected to facility power.
Ensure the AC power cord (PS0 or PS1) is connected to the rear of
the switch and a facility power receptacle. If not, connect the cord as
directed by the customer.
a. Ensure the associated facility circuit breaker is on. If not, ask the
customer set the circuit breaker on.
Event
Code
Explanation Action
200 Power supply AC voltage failure. Go to step 6.
201 Power supply DC voltage failure. Go to step 10.
202 Power supply thermal failure. Go to step 10.
208 Power supply false shutdown. Go to step 6.