McDATA 3232 Switch User Manual


 
3
3-68
McDATA® Sphereon 3032 and 3232 Fabric Switches Installation and Service Manual
Diagnostics
A blinking red and yellow diamond (failed FRU indicator)
appears at the Product View or Hardware View.
An event code recorded at the Sphereon 3032/3232 Event Log or
the SANpilot event log.
•A Failed or Not Installed message associated with a fan at the
SANpilot interface.
1
Was an event code 300, 301, 302, 303, 304, 305; or 604,: or 800,
801, 802, 806, 807, 810, 811, 812, or 850 observed at the Sphereon
3032/3232 Event Log (EFC Server) or at the SANpilot event log?
YES NO
Go to step 3.
2
The following table lists event codes, brief explanations of the codes,
and associated steps that describe fault isolation procedures.
Event
Code
Explanation Action
300 First cooling fan failed. Go to step 8.
301 Second cooling fan failed. Go to step 8.
302 Third cooling fan failed. Go to step 8.
303 Fourth cooling fan failed. Go to step 8.
304 Fifth cooling fan failed (does not apply to Sphereon
3032/3232).
Go to step 8.
305 Sixth cooling fan failed (does not apply to Sphereon
3032/3232).
Go to step 8.
604 SBAR assembly failure. Go to step 14.
800 High-temperature warning (port module sensor) Go to step 8.
801 Critically hot temperature warning (port module
thermal sensor)
Go to step 8.
802 Port module shutdown due to thermal violations. Go to step 8.
805 High-temperature warning (SBAR module thermal
sensor).
Go to step 8.