6.6 Operation frequency
6.6.1 Starting frequency
: Starting frequency setting
Function
The frequency set with the parameter is put out immediately on completion of frequency set-
ting.
Use the parameter when a delay in response of starting torque according to the accelera-
tion/deceleration time is probably affecting operation. Setting the starting frequency to a value from 0.5
to 2Hz (maximum: 5Hz) is recommended. The occurrence of an overcurrent can be suppressed by
setting this frequency below the rated slippage of the motor.
[Parameter setting]
Title Function Adjustment range Default setting
Starting frequency setting
0.5 10.0 (Hz)
0.5
Output frequency [Hz]
Starting frequency setting
Time [sec]