Toshiba VF-S9 Power Supply User Manual


 
E6580757
D-3
4
4.1.1 How to set the basic parameters
Basic parameters
All of the basic parameters can be set by the same step procedures.
Switches to the setting monitor mode.
* The inverters are
shipped from the
factory with set
parameters by default.
* Select the parameter to
be changed from "Table
of parameters".
* If there is something
that you do not
understand during the
operation, press the
MON key to return to
the indication.
Reads the programmed parameter
setting.
Saves the changed value of the
parameter setting.
Selects parameter to be changed.
Changes the parameter setting.
[Steps in key entry for basic parameters]
Steps in setting are as follows (the example shown is one of changing the maximum frequency from 80Hz to
60Hz).
Key operated LED display Operation
Displays the operation frequency (operation stopped). (When stan-
dard monitor display selection is set to 0 [operation fre-
quency]).
Press the MON key to display the first basic parameter
(automatic acceleration/deceleration).
Press either the key or the key to select " ".
Pressing the ENTER key reads the maximum frequency.
Press the key to change the maximum frequency to 60Hz.
Press the ENTER key to save the changed maximum frequency.
and frequency are displayed alternately.
After this,
Displays the same
programmed pa-
rameter.
Switches to the
display in the
status monitor
mode.
Displays names
of other parame-
ters.