Do not install in any location of high temperature, high humidity,
moisture condensation and freezing and avoid locations where
there is exposure to water and/or where there may be large
amounts of dust, metallic fragments and oil mist.
Do not install in any location where corrosive gases or grinding
fluids are present.
Operate in areas where ambient temperature ranges from -10°C to 60°C.
(Operation over 40°C is allowed when peel off the top warning label. And operation over 50°C is al-
lowed when reduce to 70°C or less of rated current.)
Measurement
position
Measurement
position
5cm 5cm
5cm
Note: The inverter is a heat-emitting body. Make sure to provide proper space and ventilation when install-
ing in the cabinet. When installing inside a cabinet, we recommend peel of the top seal although
40°C or less.
Do not install in any location that is subject to large amounts of vibration.
Note: If the VF-S9 Inverter is installed in a location that is subject
to vibration, anti-vibration measures are required. Please
consult with Toshiba about these measures.
If the VF-S9 Inverter is installed near any of the equipment listed below, provide measures to insure
against errors in operation.
Solenoids: Attach surge suppressor on coil.
Brakes: Attach surge suppressor on coil.
Magnetic contactors: Attach surge suppressor on coil.
Fluorescent lights: Attach surge suppressor on coil.
Resistors: Place far away from VF-S9 Inverter.