E6580757
A-17
1
• Do not install in any location of high temperature, high humidity,
moisture condensation and freezing and avoid locations where
there is exposure to water and/or where there may be large
amounts of dust, metallic fragments and oil mist.
• Do not install in any location where corrosive gases or grinding
fluids are present.
• Operate in areas where ambient temperature ranges from -10°C to 60°C.
(Operation over 40°C is allowed when peel off the top warning label. And operation over 50°C is al-
lowed when reduce to 70°C or less of rated current.)
Measurement
position
Measurement
position
5cm 5cm
5cm
Note: The inverter is a heat-emitting body. Make sure to provide proper space and ventilation when install-
ing in the cabinet. When installing inside a cabinet, we recommend peel of the top seal although
40°C or less.
• Do not install in any location that is subject to large amounts of vibration.
Note: If the VF-S9 Inverter is installed in a location that is subject
to vibration, anti-vibration measures are required. Please
consult with Toshiba about these measures.
• If the VF-S9 Inverter is installed near any of the equipment listed below, provide measures to insure
against errors in operation.
Solenoids: Attach surge suppressor on coil.
Brakes: Attach surge suppressor on coil.
Magnetic contactors: Attach surge suppressor on coil.
Fluorescent lights: Attach surge suppressor on coil.
Resistors: Place far away from VF-S9 Inverter.