3.2 Simplified Operation of the VF-S9
The procedures for setting operation frequency and the methods of operation can be selected from the following.
Run / stop :
(1) Run and stop using external signals to the terminal
board
(2) Run and stop from the operation panel
Frequency setting
:
(1) Setting using external signals to the terminal board
(0-10Vdc, 4-20mAdc)
(2) Setting using the operation panel
(3) Setting using the potentiometer on the inverter
main unit
Use the basic parameters (command mode selection) and (frequency setting mode selection)
for selecting.
Title Function Adjustment range Default setting
Command mode selection 0: Terminal board; 1: Operation panel 1
Frequency setting mode
selection
0: Terminal board; 1: Operation panel;
2: Internal potentiometer
2
[Steps in setting parameters]
Key operated LED display Operation
Displays the operation frequency (operation stopped). (When standard
monitor display selection is set to [Operation frequency])
Press the MON key to display the first basic parameter
(automatic acceleration/deceleration).
Press either the key or the key to select " ."
Press the ENTER key to display the parameter setting. (Standard default
setting: )
Change the parameter to (Terminal board) by pressing the key.
Press the ENTER key to save the changed parameter. and the
parameter set value are displayed alternately.
Press either the key or the key to select " ."
Press the ENTER key to display the parameter setting. (Standard default
setting: )
Change the parameter to (Operation panel) by pressing the key
Press the ENTER key to save the changed parameter. and the
parameter set value are displayed alternately.
* Pressing the MON key twice returns the display to standard monitor mode (displaying operation frequency).