Toshiba VF-S9 Power Supply User Manual


 
E6580757
F-47
6
Title Function Adjustment range Default setting
Small current trip selection
0: Disabled
1: Enabled
0
Small current (trip/alarm) detection current
0 100 (%)
0
Small current (trip/alarm) detection time
0 255 (s)
0
6.15.8 Over-torque trip
: Over-torque trip selection
: Over-torque (trip/alarm) level
: Over-torque (trip/alarm) detection time
: Over-torque (trip/alarm) level hysterisis
Function
Use the parameter to trip the inverter if a torque current exceeding the -specified
level flows for more than the -specified time. Trip information is displayed as " ".
(No trip)...... No tripping (FL relay deactivated).
An overtorque alarm can be put out to the output terminal by setting the output
terminal function selection parameter.
(Trip) .......... The inverter is tripped (FL relay activated) only after a torque current exceeding
the
-specified level has been detected for more than the -
specified time.
Title Function Adjustment range Default setting
Over-torque trip selection
0: Disabled
1: Enabled
0
Over-torque (trip/alarm) level
0 250 (%)
150
Over-torque (trip/alarm) detection time
0.00 10.0 (s)
0.5
Over-torque (trip alarm) level hysterisis
0 100 (%)
10