Toshiba VF-S9 Power Supply User Manual


 
E6580757
F-5
6
1) Standby on when ST is on
F-CC
Motor speed
Coast stop
Use this setting if an ST (standby)
terminal is required.
* The ST terminal is not assigned
as standard default setting.
Assign the ST function to an
idle input terminal by the input
terminal selection.
ST-CC
2) Standby always on (Default setting)
The inverter enters a standby status, irrespective of the ST signal status. Motor rotation stops according to
the selected deceleration time at the set frequency.
3) Interlocked with F/R
F-CC
Motor speed
Coast stop
Turning the operation
signal (F/R) off causes
the motor to coast to a
stop.
4) Standby on when ST is off
Inversion of item 1) above.
6.2.2 Setting the reset signal
: RST (reset) signal selection
Function
The parameter specifies reset function activation timing, depending on the particular status of
the RST (reset) signal.
1) Standard setting (reset on when RST-CC on to off)
2) Activated by turning RST off (reset on when RST-CC off to on)
This parameter is available in the modifying input terminal functions (
) = 10 (RST).
To reset the protective function on the parameter setting
, do any of the following.
1. Turn off the power.
2. Press the STOP key twice while the protection function is displayed.
3. Turn on and off the error reset control input signal.