E6580757
E-12
5
Short across the R-CC terminals: reverse rotation
* Reverse rotation is valid if short across the F-CC terminals and R-CC terminals at the same time.
★ This function is valid only when is set to 1 (operation panel).
5.9 Maximum frequency
: Maximum frequency
• Function
1) Programs the range of frequencies output by the inverter (maximum output values).
2) This frequency is used as the reference for acceleration/deceleration time.
Frequency setting signal (%)
• This function determines the
maximum value in line with the
ratings of the motor and load.
• Maximum frequency cannot be
adjusted during operation. To
adjust, first stop the inverter.
When
Output frequency
(
Hz
)
When
★ If is increased, adjust the upper limit frequency as necessary.
■ Parameter setting
Title Function Adjustment range Default setting
Maximum frequency
30.0 ∼ 400 (Hz)
80.0
5.10 Upper limit and lower limit frequencies
: Upper limit frequency
: Lower limit frequency
• Function
Programs the lower limit frequency that determines the lower limit of the output frequency and the upper
limit frequency that determines the upper limit of that frequency.