Toshiba VF-S9 Power Supply User Manual


 
E6580757
K-11
11
Table of output terminal functions (2/2)
Function
No.
Code Function Action
15 RUNN Inversion of RUN/STOP Inversion of RUN setting
16 POL OL pre-alarm ON: 50% or more of calculated value of overload
protection level
OFF: Less than 50% of calculated value of over-
load protection level
17 POLN Inversion of OL pre-alarm Inversion of POL setting
18 POHR Braking resistor overload pre-alarm ON: 50% or more of calculated value of set
overload protection level
OFF: Less than 50% of calculated value of
set overload protection level
19 POHRN Inversion of braking resistor overload pre-alarm Inversion of POHR setting
20 POT Over-torque detection pre-alarm ON: Torque current is equal to or larger than 70%
of set value.
OFF: Torque current is smaller than 70% of
set value.
21 POTN Inversion of over-torque detection pre-alarm Inversion of POT setting
22 PAL Pre-alarm ON: When POL, POHR or POT is on, or , or
issues an alarm
OFF: When POL, POHR and POT are off, and ,
and issue no alarm
23 PALN Inversion of pre-alarm Inversion of PAL setting
24 UC Low-current detection ON: Output current is equal to or larger than
set value and longer than set time.
OFF: Output current is smaller than set
value.
25 UCN Inversion of low-current detection Inversion of UC setting
26 HFL Hard fault ON: Tripping ( , , , , ,
, , , , ,
, )
OFF: Failure other than the above
27 HFLN Inversion of hard fault Inversion of HFL setting
28 LFL Soft fault ON: Tripping ( , , , ,
, )
OFF: Failure other than the above
29 LFLN Inversion of soft fault Inversion of LFL setting