How to install
Danger
Prohibited
Do not install and operate the inverter if it is damaged or any component is missing.
This can result in electric shock or fire. Please consult your local agency for repairs.
Mandatory
Must be installed in nonflammables such as metals.
The rear panel gets very hot so that if installation is in an inflammable object, this can result in fire.
Do not operate with the front panel cover removed. This can result in electric shock.
An emergency stop device must be installed that fits with system specifications (e.g. cuts off input
power then engages mechanical brakes).
Operation cannot be stopped immediately by the inverter alone, thus risking an accident or injury.
All options used must be those specified by Toshiba. The use of any other option may result in an acci-
dent.
Warning
Mandatory
The main unit must be installed on a base that can bear the unit's weight.
If the unit is installed on a base that cannot withstand that weight, the unit may fall resulting in injury.
If braking is necessary (to hold motor shaft), install a mechanical brake. The brake on the inverter will
not function as a mechanical hold, and if used for that purpose, injury may result.
Installation location
Select a location with good indoor ventilation, place lengthwise in the vertical direction and attach to a metal
wall surface.
If you are installing more than one inverter, the separation between inverters should be at least 5 centime-
ters, and they should be arranged in horizontal rows.
If the inverters are horizontally arranged with no space between them (side-by-side installation), peel of the
ventilation seals on top of the inverters and operate at 40°C or less (model of 3.7kW or less). Operate at
50°C or less (model of 5.5kW or more).
Standard installation
5 centimeters
or more
Horizontal installation (side-by-side installation)
10 centimeters
or more
10 centimeters or
more
Remove seals on
top
A
mbient temperature of 40°C or less (model of 3.7kW or less)
Ambient temperature of 50°C or less (model of 5.5kW or more).
5 centimeters
or more
10 centimeters
or more
VFS9 VFS9 VFS9 VFS9
The space shown in the diagram is the minimum allowable space. Because air cooled equipment has cooling
fans built in on the top or bottom surfaces, make the space on top and bottom as large as possible to allow