Toshiba VF-S9 Power Supply User Manual


 
E6580757
K-3
11
Title Communication
No.
Function Unit Minimum
setting unit
Adjustment range Default
setting
User
setting
Reference
0110 Always-active
function selection
- - 0-51 0 6.3.1
0111 Input terminal
selection 1 (F)
- - 0-51 (F) 2 6.3.2
0112 Input terminal
selection 2 (R)
- - 0-51 (R) 3 6.3.2
0113 Input terminal
selection 3 (RST)
- - 0-51 (RST) 10 6.3.2
0114 Input terminal
selection 4 (S1)
- - 0-51 (SS1) 6 6.3.2
0115 Input terminal
selection 5 (S2)
- - 0-51 (SS2) 7 6.3.2
0116 Input terminal
selection 6 (S3)
- - 0-51 (SS3) 8 6.3.2
0130 Output terminal
selection 1
(RY-RC)
- - 0-29 (LOW) 4 6.3.3
0131 Output terminal
selection 2 (OUT)
- - 0-29 (RCH) 6 6.3.3
0132 Output terminal
selection 3 (FL)
- - 0-29 (FL) 10 6.3.3
0170 Base frequency 2 Hz 0.1 25-400 *1 6.4.1
0172 Torque boost 2 %/(V) 0.1 0.0-30.0 *2 6.4.1
0173 Motor
electronic-thermal
protection level 2
%/(A) 1 10-100 100 6.4.1
Frequency parameters
Title Communication
No.
Function Unit Minimum
setting unit
Adjustment range Default
setting
User
setting
Reference
0200 Frequency priority
selection
- - 0: VIA/II, VIB
1: VIB, VIA/II
2: External switching
(FCHG enabled)
3: External contact UP/DOWN *5
4: External contact UP/DOWN *5
(Setting retained even if the power
is turned off)
5: VIAI/II + VB
0 6.5.1
0201 VIA/II input point 1
setting
% 1 0-100 0 6.5.2
0202 VIA/II input point 1
frequency
Hz 0.1 0.0-400.0 0.0 6.5.2
0203 VIA/II input point
2setting
% 1 0-100 100 6.5.2
0204 VIA/II input point
2frequency
Hz 0.1 0.0-400.0 *1 6.5.2
0210 VIB input point 1
setting
% 1 0-100 0 6.5.2
Frequency UP
response time *5
(0.1s) 1 0-100 0
0211 VIB input point 1
frequency
Hz 0.1 0.0-400.0 0.0 6.5.2
Frequency UP
step width *5
0.1 0.0-400.0 0.0
0212 VIB input point 2
setting
% 1 0-100 100 6.5.2
Frequency DOWN
response time *5
(0.1s) 1 0-100 100
*5 : Set the parameter to or ,function of is bottom of paragraph.