Toshiba VF-S9 Power Supply User Manual


 
E6580757
K-10
11
Table of input terminal functions (3/3)
Function
No.
Code Function Action
45 EXTN Inversion of trip stop command from external de-
vice
OFF: -trip stop
46 OH Thermal trip stop signal input from external device ON: trip stop
47 OHN Inversion of thermal trip stop command from ex-
ternal device
OFF: trip stop
48 SC/LC Remote/local control forced switching Enabled when remote control is exercised
ON: Local control
(setting of and )
OFF: Remote control
49 HD Operation holding (stop of 3-wire operation) ON: F (forward run)/R: (reverse run) held, 3-wire
operation
OFF: Slowdown stop
50 SDBF Forward run after DC braking ON: Forward run after DC braking
OFF: Slowdown stop
51 SDBR Reverse run after DC braking ON: Reverse run after DC braking
OFF: Slowdown stop
Table of output terminal functions (1/2)
Function
No.
Code Function Action
0 LL Frequency lower limit ON: Output frequency is equal to or higher than
value.
OFF: Output frequency is lower than
value.
1 LLN Inversion of frequency lower limit Inversion of LL setting
2 UL Frequency upper limit ON: Output frequency is equal to or higher than
value.
OFF: Output frequency is lower than
value.
3 ULN Inversion of frequency upper limit Inversion of UL setting
4 LOW Low-speed detection signal ON: Output frequency is equal to or higher than
set value.
OFF: Output frequency is lower than
set value.
5 LOWN Inversion of low-speed detection signal Inversion of LOW setting
6 RCH Designated frequency reach signal (completion of
acceleration/deceleration)
ON: Output frequency is within (input frequency
± set frequency).
OFF: Output frequency exceeds (input frequency
± set frequency).
7 RCHN Inversion of designated frequency reach signal
(inversion of completion of acceleration/
deceleration)
Inversion of RCH setting
8 RCHF Set frequency reach signal ON: Output frequency is within
( set frequency ± set
frequency).
OFF: Output frequency exceeds
( set frequency ± set
frequency).
9 RCHFN Inversion of set frequency reach signal Inversion of RCHF setting
10 FL Failure FL (trip output) ON: When inverter is tripped
OFF: When inverter is not tripped
11 FLN Inversion of failure FL (inversion of trip output) Inversion of FL setting
12 OT Over-torque detection ON: Torque current is equal to or larger than
set value and longer than set time.
OFF: Torque current is lower than set
value.
13 OTN Inversion of over-torque detection Inversion of OT setting
14 RUN RUN/STOP ON: When operation frequency is output or during
DC braking ( )
OFF: Operation stopped