5
I
Warning
See item
Prohibited
Observe all permissible operating ranges of motors and mechanical equipment. (Refer to
the motor's instruction manual.) Not observing these ranges may result in injury.
3.
When sequence for restart after a momentary power failure is selected
(inverter)
Warning
See item
Mandatory
Stand clear of motors and mechanical equipment
If the motor stops due to a momentary power failure, the equipment will start suddenly af-
ter power recovers. This could result in unexpected injury.
Attach warnings about sudden restart after a momentary power failure on inverters, mo-
tors and equipment for prevention of accidents in advance.
6.12.1
6.12.1
When retry function is selected (inverter)
Warning
See item
Mandatory
Stand clear of motors and equipment.
If the motor and equipment stop when the alarm is given, selection of the retry function will
restart them suddenly after the specified time has elapsed. This could result in unex-
pected injury.
Attach warnings about sudden restart in retry function on inverters, motors and equipment
for prevention of accidents in advance.
6.12.3
6.12.3
Maintenance and inspection
Danger
See item
Prohibited
Do not replace parts.
This could be a cause of electric shock, fire and bodily injury. To replace parts, call the lo-
cal sales agency.
14.2
Mandatory
The equipment must be inspected every day.
If the equipment is not inspected and maintained, errors and malfunctions may not be dis-
covered and that could result in accidents.
Before inspection, perform the following steps.
(1) Turn off all input power to the inverter.
(2) Wait for at least ten minutes and check to make sure that the charge lamp is no longer
lit.
(3) Use a tester that can measure DC voltages (800VDC or more), and check to make
sure that the voltage to the DC main circuits (across PA-PC) is 45V or less.
If inspection is performed without performing these steps first, it could lead to electric
shock.
14.
14.