E6580757
K-7
11
Title Communication
No.
Function Unit Minimum
setting unit
Adjustment range Default
setting
User
setting
Reference
0608 Input phase failure
detection mode
selection
- - 0: Disabled
1: Enabled
1 6.15.6
0610 Small current trip
selection
- - 0: Disabled
1: Enabled
0 6.15.7
0611 Small current
(trip/alarm)
detection current
% 1 0-100 0 6.15.7
0612 Small current
(trip/alarm) detec-
tion time
s 1 0-255 0 6.15.7
0615 Over-torque trip
selection
- 0: Disabled
1: Enabled
0 6.15.8
0616 Over-torque
(trip/alarm) level
% 1 0-200 150 6.15.8
0618 Over-torque
detection time
s 0.1 0-10 0.5 6.15.8
0619 Over-torque (trip
alarm) level
hysterisis
% 1 0-100 10 6.15.8
0627 Undervoltage trip
selection
- - 0: Disabled
1: Enabled (Trip at 70% or less)
2: Disabled (Stop (not trip) at 50% or
less)
0 6.15.9
0692 Meter bias % 1 0-50 0 6.15.10
• Operation panel parameters
Title
Communication
No.
Function Unit Minimum
setting unit
Adjustment range Default
setting
User
setting
Reference
0700
Prohibition of
change of
parameter settings
- - 0: Permitted ( and
cannot be changed during
operation.)
1: Prohibited
2: Permitted ( and
also can be changed during
operation.)
0 6.16.1
0701
Unit selection - - 0: No change
1: % Æ A (ampere)/V (volt)
2: Free unit selection enabled
( )
3: % Æ A (ampere)/V (volt)
Free unit selection enabled
( )
0 6.16.2
0702
Free unit selection - 0.01 0.01-200.0 1.00 6.16.2
0710
Standard monitor
display selection
- - 0: Operation frequency (Hz/free unit)
1: Output current (%/A)
2. Frequency command (Hz/free unit)
3: Inverter rated current (A)
4: Inverter over load factor (%)
5: Output power (%)
0 6.16.3
• Communication parameters
Title
Communication
No.
Function Unit Minimum
setting unit
Adjustment range Default
setting
User
setting
Refer-
ence
0800
Communication
band speed
- - 0:1200bps , 1:2400bps , 2:4800bps
3:9600bps , 4:19200bps
36.17
0801
Parity - - 0:NON, 1:EVEN, 2:ODD 1 6.17
0802
Inverter number - 1 0-63 0 6.17
0803
Communication
error trip time
s 1 0 (Disabled) , 1-100 0 6.17