[Parameter setting]
Title Function Adjustment range Default setting
DC braking starting frequency 0.0 (Hz) 0.0
DC braking current 0.0 100 (%) 30.0
DC braking time 0.0 20.0 (sec) 1.0
DC braking starting frequency
Output frequency [Hz]
Set frequency
Output current [A]
DC braking
Time [sec]
DC braking current
DC braking time
Operation signal (F-CC)
Note: During DC braking, the overload protection sensitivity of the inverter increases. The DC braking cur-
rent may be adjusted automatically to prevent tripping.
6.8 Jog run mode
: Jog run frequency
: Jog run stopping pattern
Function
Use the jog run parameters to operate the motor in jog mode. Input of a jog run signal generates a jog
run frequency output at once, irrespective of the designated acceleration time.
The motor can be operated in jog mode while the jog run setting terminals are connected (RST-CC ON).(Setting
to .)