Toshiba VF-S9 Power Supply User Manual


 
E6580757
D-7
4
4.1.4 How to program setup parameters
Setu
p
p
arameters
When the standard parameter is set to (standard default setting), the setup parameter is displayed.
Setting the setup parameter enable to operate.
The setup parameter selects either 50Hz or 60Hz for the base motor frequency.
Set this in line with the specifications of the motor.
The setup parameters automatically program the base motor frequency and related parameters, but those
parameters can be reprogrammed later.
The steps in setting are as follows
Key operated LED display Operation
Displays the base motor frequency.
Press either the key or the key to select 50Hz or 60Hz.
Press the ENTER key to set the base motor frequency and related pa-
rameters.
will be displayed during the setting.
Displays the operation frequency (while stopped)
Setting of the following parameters can be changed by the setup parameters.
They are displayed as changed parameters during
searches .
If select of 60Hz, and are not displayed as changed parameters.
Setting value 50 60
Title Function Setting value
Upper limit frequency 50Hz 60Hz
Base frequency 1 50Hz
60Hz
(Standard)
Base frequency 2 50Hz
60Hz
(Standard)
Frequency at VIA input point 2 50Hz 60Hz
Frequency at VIB input point 2 50Hz 60Hz