Toshiba VF-S9 Power Supply User Manual


 
E6580757
E-9
5
Adjustment scale with meter adjustment
parameter
Connect meters as shown below.
Meter: frequency meter
(default setting)
<Ammeter>
The reading of the
frequency meter
will fluctuate during
scale adjustment.
Make the maximum ammeter scale at least 150
percent of the inverter's rated output current
Optional frequency meter: QS-60T
<Frequency meter>
The reading of the
frequency meter
will fluctuate during
scale ad
j
ustment.
Meter: ammeter
( = 1)
[Connected meter selection parameters]
Title Function Adjustment range Default setting
Meter selection
0: Output frequency
1: Output current
2: Set frequency
3: For adjustment (current fixed at 100%)
4: Inverter load factor
5: Output power
0
Meter adjustment - -
Resolution
All FM terminals have a maximum of 1/256
Example of 4-20mA programmed output (for details, see 6.15.10)
Set the
if adjusting the bias.