6.5.2 Setting frequency command characteristics
: VIA/II input point 1 setting
: VIA/II input point 1 frequency
: VIA/II input point 2 setting
: VIA/II input point 2 frequency
: VIB input point 1 setting (Frequency UP response time)
: VIB input point 1 frequency (Frequency UP step width)
: VIB input point 2 setting (Frequency DOWN response time)
: VIB input point 2 frequency (Frequency DOWN step width)
Function
These parameters adjust the output frequency according to the externally applied analog signal
(0-10V dc voltage, 4-20mA dc current) and the entered command for setting an external contact
frequency.
Parameter setting
Title Function Adjustment range Default setting
VIA/II input point 1 setting
0 100 (%)
0
VIA/II input point 1 frequency
0.0 400.0 (Hz)
0.0
VIA/II input point 2 setting
0 100 (%)
100
VIA/II input point 2 frequency
0.0 400.0 (Hz)
50 or 60 *1
VIB input point 1 setting
0 100 (%)
0
Frequency UP response time
0 100 (1: 0.1 s)
0
VIB input point 1 frequency
0.0 400.0 (Hz)
0.0
Frequency UP step width
0.0 400.0
0
VIB input point 2 setting
0 100 (%)
100
Frequency DOWN response time
0 100 (1: 0.1 s)
100
VIB input point 2 frequency
0.0 400.0 (Hz)
50 or 60 *1
Frequency DOWN step width
0.0 400.0
50 or 60 *1
Note1) Setting value of and depending on the end of Type form. AN, WN : 60Hz, WP: 50Hz.
Note2)
~ can be used as UP/DOWN function depend on the setting.
Note3) Don't set the same value between point 1 and point 2.
If set the same value, the
is displayed.