Selection of wiring devices
Non-fuse circuit
breaker
(MCCB)
Magnetic contactor
(MC)
Overload relay
(THR)
Earth leakage
breaker
(ELCB)
Voltage class
Capacity of
applicable
motor
(kW)
Inverter model
Rated
current
(A)
Type
Note1)
Rated
current
(A)
Type
Note1)
Adjusted current
(A)
(For reference)
Type
Note1)
Rated
current
(A)
Type
Note1)
0.2 VFS9S-2002PL 10 NJ30N 11 C11J 1.3 T13J 10 NJV50E
0.4 VFS9S-2004PL 15 NJ30N 11 C11J 2.3 T13J 15 NJV50E
0.75 VFS9S-2007PL 20 NJ30N 11 C11J 3.6 T13J 20 NJV50E
1.5 VFS9S-2015PL 30 NJ30N 18 C20J 6.8 T13J 30 NJV50E
Single-phase
200V class
2.2 VFS9S-2022PL 40 NJ50E 35 C35J 9.3 T13J 40 NJV50E
0.2 VFS9-2002PM 5 NJ30N 11 C11J 1.3 T13J 5 NJV50E
0.4 VFS9-2004PM 5 NJ30N 11 C11J 2.3 T13J 5 NJV50E
0.75 VFS9-2007PM 10 NJ30N 11 C11J 3.6 T13J 10 NJV50E
1.5 VFS9-2015PM 15 NJ30N 11 C11J 6.8 T13J 15 NJV50E
2.2 VFS9-2022PM 20 NJ30N 13 C13J 9.3 T13J 20 NJV50E
3.7 VFS9-2037PM 30 NJ30N 26 C25J 15 T20J 30 NJV50E
5.5 VFS9-2055PL 50 NJ50E 35 C35J 22 T35J 50 NJV50E
7.5 VFS9-2075PL 60 EJ100F 50 C50J 28 T35J 60 NJV60F
11 VFS9-2110PM 100 EJ100F 65 C65J 44 T65J 100 NJV100F
Three-phase
200V class
15 VFS9-2150PM 125 EJ225F 80 C80A 57 T65J 125 NJV225F
0.75 VFS9-4007PL 5 NJ30N 9 C11J 1.6 T13J 5 NJV50E
1.5 VFS9-4015PL 10 NJ30N 9 C11J 3.6 T13J 10 NJV50E
2.2 VFS9-4022PL 15 NJ30N 9 C11J 5.0 T13J 15 NJV50E
3.7 VFS9-4037PL 20 NJ30N 13 C13J 6.8 T13J 20 NJV50E
5.5 VFS9-4055PL 30 NJ30N 17 C20J 11 T13J 30 NJV50E
7.5 VFS9-4075PL 30 NJ30N 25 C25J 15 T20J 30 NJV50E
11 VFS9-4110PL 50 EJ50E 33 C35J 22 T35J 50 NJV50E
Three-phase
400V class
15 VFS9-4150PL 60 EJ100F 48 C50J 28 T35J 60 NJV100F
Note 1: Produced by Schneider Toshiba electric corporation.
Note 2: Be sure to attach a surge killer to the exciting coil of the relay and the magnetic contactor.
Selection of surge killers for Toshiba magnetic contactors
200V class: Surge absorbing units are optionally available for Toshiba C11J to C65J, or
Model SS-2 for C50J and C65J
400V class: For the operation and control circuits, regulate the voltage at 200V or less with a step-down
transformer.
Note 3: When using the auxiliary contacts 2a of the magnetic contactor MC for the control circuit, connect the
contacts 2a in parallel to increase reliability.
Of the wiring devices listed in the above table, the magnetic contactors (MC) and the overload relays (Th-Ry) are
intended for use with the Mighty J series. When using the old series (ESPER Mighty series), refer to the table
below showing the correspondence between the two series.
Magnetic contactor (MC) Overload relay
ESPER Mighty series Mighty J series ESPER Mighty series Mighty J series
C12A C13J T11A T13J
C20A C20J T20A T20J
C35A C35J T35A T35J
C50A C50J T65A T65J
C65A C65J