E6580757
A-9
1
2) Control circuit terminal board
The control circuit terminal board is common to all equipment.
FLA FLB FLC RY RC CC
VIA VIB
PP II FM F R
RST
S1 S2 S3 CC
OUT
P24
FMV
/
FMC
SOURCE
/
SINK
M3 screw
(0.5N m)
M2 screw (0.25N m)
JP302
JP301
JP301A
Case of SINK
JP301: Input
JP301A: Output
Wire size
Solid wire : 0.3 to 1.5(mm
2
)
Stranded wire
: 0.3 to 1.5(mm
2
)
(AWG 22 to 16)
Sheath strip length : 6 (mm)
Wire size
Solid wire : 0.3 to 1.5(mm
2
)
Stranded wire : 0.3 to 1.25(mm
2
)
(AWG 22 to 16)
Sheath strip length : 5 (mm)
See 2.3.2 for details on all terminal functions.
1.3.3 How to open the front (terminal board) cover
To wire the terminal board, remove the front lower cover in line with the steps given below
Remove the screw at
the right hand side of
the front cover.
Pull and lift the front
(terminal board) cover
out toward you.