Toshiba VF-S9 Power Supply User Manual


 
E6580757
I-3
9
Single-phase 200V class
Combination of inverter and filter
Inverter Filter for class A
compliance
Filter for class B
compliance
VFS9S-2002PL With a built-in filter EMFS2010AZ
VFS9S-2004PL With a built-in filter EMFS2010AZ
VFS9S-2007PL With a built-in filter EMFS2010AZ
VFS9S-2015PL With a built-in filter EMFS2016CZ
VFS9S-2022PL With a built-in filter EMFS2025DZ
(2) Use shielded cables for the power and control cables, including filter input cables and inverter output ca-
bles. Route the cables and wires so as to minimize their lengths. Keep a distance between the power ca-
ble and the control cable and between the input and output wires of the power cable. Do not route them in
parallel or bind them together, instead cross at right angle.
(3) Install the inverter and the filter on the same metal plate. It is more effective in limiting the radiation noise to
install the inverter in a sealed steel cabinet. Using wires as thick and short as possible, earth the metal
plate and the control panel securely with a distance kept between the earth cable and the power cable.
(4) Route the EMI filter input and output wires apart from each other.
(5) To limit the radiation noise from cables, earth each shielded cable to the metal plate. It is effective to earth
shielded cables in the vicinity of the inverter, cabinet and filter (within a radius of 10cm from each of them).
Inserting a ferrite core in a shielded cable is even more effective in limiting the radiation noise.
(6) To further limit the radiation noise, insert a zero-phase reactor in the inverter output line and insert ferrite
cores in the earth cables of the metal plate and cabinet.
[Example of wiring]
VF-S9
Grounding plate
Control wiring (Shielded cables)
(Note 1)
FL relay wiring
Grounding terminal
screw
RY relay wiring
Power supply
w
iring
(shielded cables)
Motor wiring (Shielded cables)
Note 1: Strip and earth the shielded cable, following the example shown in Fig.