Toshiba VF-S9 Power Supply User Manual


 
E6580757
M-3
13
(Continued)
Error code
Communication
No.
Problem Possible causes Remedies
* 1D Small-current opera-
tion trip
The output current falls to the low-current
detection level during operation.
Enable (low-current detection pa-
rameter).
Check whether the detection level is set
properly to the system.
( and )
If no error is found in the setting, make a
service call.
22h Ground fault trip
A ground fault occurs in the output cable
or the motor.
Check the cable and the motor for ground
faults.
11h Emergency stop
During automatic operation or remote op-
eration, a stop command is entered from
the operation panel or a remote input de-
vice.
Reset the inverter.
15h
Main unit RAM fault
The control RAM is defective. Make a service call.
16h
Main unit ROM fault
The control ROM is defective. Make a service call.
17h
CPU fault trip
The control CPU is defective. Make a service call.
18h Remote control error
An error arises during remote operation. Check the remote control device, cables,
etc.
29h Inverter type error
The control circuit board (main circuit
board or drive circuit board) is replaced.
Make a service call.
12h EEPROM fault
A data writing error occurs. Turn off the inverter, then turn it on again.
If it does not recover from the error, make
a service call.
28h Auto-tuning error
Check the settings of the motor parameters to .
Check that the motor is not two or more sizes smaller in capacity than the inverter.
Check that the inverter output cable is not too thin.
Check that the motor is not running.
Check that the motor is a three-phase inductive motor.
* With a parameter, you can choose between trip-on and -off.
[Alarm information] Each message in the table is displayed to give a warning but does not cause the inverter to
trip.
Error code Problem Possible causes Remedies
(Note 1)
ST terminal OFF
The ST-CC circuit is opened. Close the ST-CC circuit.
Undervoltage in main
circuit
The supply voltage between R, S and T is
under voltage.
Measure the main circuit supply voltage.
If the voltage is at a normal level, the
inverter requires repairing.
Retry in process
The inverter is in the process of retry.
A momentary stop occurred.
The inverter is normal if it restarts after
several tens of seconds.
The inverter restarts automatically. Be
careful of the machine because it may
suddenly restart.
Frequency point set-
ting error
The frequency setting signals at points 1
and 2 are set too close to each other.
Set the frequency setting signals at points
1 and 2 apart from each other.
Clear command ac-
ceptable
This message is displayed when pressing
the STOP key while an error code is dis-
played.
Press the STOP key again to clear the
trip.
Emergency stop
command accept-
able
The operation panel is used to stop the
operation in automatic control or remote
control mode.
Press the STOP key for an emergency
stop.
To cancel the emergency stop, press any
other key.
Setting error alarm /
An error code and
data are displayed
alternately twice
each.
An error is found in a setting when data is
reading or writing.
Check whether the setting is made cor-
rectly.
(Continued overleaf)