Toshiba VF-S9 Power Supply User Manual


 
E6580757
F-31
6
6.12.6 Output voltage adjustment/Supply voltage correction
: Output voltage adjustment (Base frequency voltage)
: Supply voltage correction
Function
Output voltage adjustment (Base frequency voltage)
The parameter adjusts the voltage corresponding to the base frequency 1 so that no
voltage exceeding the set value is put out. (This function is enabled only when is
set to either "0", "1", or "2".)
Supply voltage correction
The parameter maintains a constant V/F ratio, even when the input voltage decreases. The
torque during low-speed operation is prevented from decreasing.
Supply voltage correction .............. Maintains a constant V/F ratio, even when the input voltage fluctuates.
Output voltage adjustment............. Limits the voltage at frequencies exceeding the base frequency. Applied
when operating a special motor with low induced voltage.
[Parameter setting]
Title Function Adjustment range Default setting
Output voltage adjustment
(Base frequency voltage)
0 250 (V), 0 500 (V)
200V/400V
Supply voltage correction
0: Supply voltage uncorrected,
output voltage limited
1: Supply voltage corrected,
output voltage limited
2: Supply voltage corrected (off during slow-
down), output voltage limited
3: Supply voltage uncorrected,
output voltage unlimited
4: Supply voltage corrected,
output voltage unlimited
5: Supply voltage corrected (off during decel-
eration), output voltage unlimited
1
If is set to "0" or "3", the output voltage will change in proportion to the input voltage.
Even if the base frequency voltage (
parameter) is set above the input voltage, the output voltage
will not exceed the input voltage.
The rate of voltage to frequency can be adjusted according to the rated motor capacity. For example,
setting
to " " or " " prevents the output voltage from increasing, even if the input voltage
changes when operation frequency exceeds the base frequency.