E6580757
K-1
11
11. Table of parameters and data
11.1 User parameters
Title Function Unit Minimum
setting unit
Adjustment range Default
setting
User
setting
Reference
- Applicable motor
base frequency *3
Hz - 60
50
*1 4.1
Operation
frequency of
operation panel
Hz 0.1 - 0.0 3.2
*3 : When the standard setting ( : ) is entered, this parameter displayed.
11.2 Basic parameters
• Four automatic functions
Title Communication
No.
Function Unit Minimum
setting unit
Adjustment range Default
setting
User
setting
Reference
0000 Automatic
acceleration/
deceleration
- - 0: Disabled (manual)
1: Optimum rate
2: Minimum rate
05.1
0001 Automatic torque
boost
- - 0: Disabled
1: Vector control + auto-tuning
05.2
0002 Automatic
environment
setting
- - 0: Disabled
1: Automatic setting
05.3
0040 Automatic function
setting
- - 0: Disabled
1: Coast stop
2: 3-wire operation
3: External input UP/DOWN setting
4: 4-20 ma current input operation
05.4
• Other basic parameters
Title Communication
No.
Function Unit Minimum
setting unit
Adjustment range Default
setting
User
setting
Reference
0003 Command mode
selection
- - 0: Terminal board
1: Operation panel
15.5
0004 Frequency setting
mode selection
- - 0: Terminal board
1: Operation panel
2: Internal potentiometer
25.5
0005 Meter selection - - 0: Output frequency
1: Output current
2: Set frequency
3: For adjustment (current fixed at
100%)
4: Inverter load factor
5: Output power
05.6
0006 Meter adjustment - - - 5.6
0007 Standard setting
mode selection
--
0 ∼ 2: -(invalid)
3: Default setting
4: Trip clear
5: Cumulative operation time clear
6: Initialization of type information
05.7
*1 : The end of type – form depend
AN – WN : 60Hz
WP : 50Hz
*2 : Model depend (See section 11 page K-6)