E6580757
K-5
11
• Operation mode parameters
Title Communication
No.
Function Unit Minimum
setting unit
Adjustment range Default
setting
User
setting
Reference
0300 PWM carrier
frequency
kHz 0.1 2.0-16.5 12.0 6.11
0301 Auto-restart
control selection
- - 0: Disabled
1: At auto-restart after momentary stop
2: When turning ST-CC on or off
3: At auto-restart or when turning
ST-CC on or off
4: Motion of DC braking at start-up
(at auto-restart after momentary
stop)
5: Motion of DC braking at start-up
(when turning ST-CC on or off)
6: Motion of DC braking at start-up
(at auto-restart or when turning
ST-CC on or off)
0 6.12.1
0302 Regenerative
power ride-
through control
- - 0: Disabled
1: Enabled
0 6.12.2
0303 Retry selection
(number of times)
Times 1 0-10 0 6.12.3
0304 Dynamic braking
selection
- - 0: Dynamic braking disabled
1: Dynamic braking enabled, over-
load protection disabled
2: Dynamic braking enabled, over-
load protection enabled
0 6.12.4
0305 Overvoltage limit
operation
- - 0: Enabled
1: Prohibited
0 6.12.5
0306 Output voltage
adjustment (Base
frequency voltage)
V 1 0 to 250V, 0 to 500V
200V/400V
6.12.6
0307 Supply voltage
correction
- - 0: Supply voltage uncorrected, output
voltage limited
1: Supply voltage corrected, output
voltage limited
2: Supply voltage corrected (off dur-
ing deceleration), output voltage
limited
3: Supply voltage uncorrected, output
voltage unlimited
4: Supply voltage corrected, output
voltage unlimited
5: Supply voltage corrected (off dur-
ing deceleration), output voltage
unlimited
1 6.12.6
0308 Braking resistor
operation rate
%ED 1 1-100 3 6.12.4
0312 Random mode - - 0: Disabled
1: Enabled
06.11
0360 PI control - - 0: Disabled
1: Enabled
0 6.12.7
0362 Proportional gain - - 0-01-100.0 0.30 6.12.7
0363 Integral gain - - 0.01-100.0 0.20 6.12.7