Toshiba VF-S9 Power Supply User Manual


 
E6580757
F-42
6
3) Switching using external terminals - Switching the acceleration/deceleration time via external termi-
nals
Output frequency [Hz]
Time [sec]
(1) Acceleration at the gradient
corresponding to acceleration
time
(2) Acceleration at the gradient
corresponding to acceleration
time
(3) Deceleration at the gradient
corresponding to deceleration
time
(4) Deceleration at the gradient
corresponding to deceleration
time
(1) (2) (3) (4)
AD2 switching
In this case, set " " to 0 (terminal board).
A switching signal for the acceleration/deceleration 2 is not set as the default.
Assign function number 5 (
) to an idle terminal by specifying the input terminal function selection
parameter.
6.15 Protection functions
6.15.1 Setting motor electronic thermal protection
: Motor electronic thermal protection level 1
Function
This parameter allows selection of the appropriate electronic thermal protection characteristics ac-
cording to the particular rating and characteristics of the motor.
The " " parameter and extended parameter have the same function. Modification of
either parameter means that the same value is set for both parameters.
Parameter setting
Title Function Adjustment range Default setting
( )
Motor electronic thermal protection
level 1
10 100 (%)
100