E6580757
E-6
5
Automatically programmed functions and parameter set values
Default setting 1: Coast stop 2: 3-wire opera-
tion
3: External input
UP/DOWN set-
ting
4: 4-20mA current
input operation
2: Potentiometer 2: Potentiometer 2: Potentiometer
1: Operation
panel
0: Terminal board
1: Operation
panel
0: Terminal board 0: Terminal board 0: Terminal board 0: Terminal board
(F) 2: F 2: F 2: F 2: F 2: F
(R) 3: R 3: R 3: R 3: R 3: R
(RST) 10: RST 10: RST 10: RST 10: RST 10: RST
(S1) 6: SS1 6: SS1 6: SS1 41: UP 6: SS1
(S2) 7: SS2 7: SS2 7: SS2 42: DOWN 38: FCHG
(S3) 8: SS3 1: ST 49: HD 43: CLR 1: ST
(ST) 1: Always active
0: Activated by
turning ST on
active
1: Always active 1: Always active
0: Activated by
turning ST on
active
0: VIA/II 0: VIA/II 0: VIA/II 3: UP/DOWN 0: VIA/II
----20%
-----
-----
-----
---1-
- - - 0.1Hz -
---1-
- - - 0.1Hz -
Disabled ( )
Input terminals and parameters are standards programmed at the factory.
Coast stop ( )
Setting for coast stopping. ST (standby signal) is assigned to the S3 terminal and the operation is controlled
by the on and off of the S3 terminal.
3-wire operation ( )
Can be operated by a momentary push-button. HD (operation holding) is assigned to the terminal S3. A
self-holding of operations is made in the inverter by connecting the stop switch (b-contact) to the S3 termi-
nal and connecting the running switch (a-contact) to the F terminal or the R terminal.
External input UP/DOWN setting
( )
Allows setting of frequency with the input from an external contact. Can be applied to changes of frequen-
cies from several locations. UP (frequency up signal input from external contact) is assigned to the S1 ter-