6.15.4 External input trip stop mode selection
: External input trip stop mode selection
: Emergency DC braking time
Function
These parameters set the method of stopping the inverter in external trip stop mode. When the
inverter is stopped, the trip detection function (" " display) and the FL relay are activated. If
is set to " " (Emergency DC braking), also set (DC braking current) and
(Emergency DC braking time).
1) External trip stop via terminals
The external trip stop function can be executed via the a-contact. Proceed as follows to assign an external
stopping terminal and select the stopping method:
Input terminal
CC
a-contact
[Parameter setting]
Title Function Adjustment range Default setting
External input trip stop mode selection
0: Coast stop
1: Slowdown stop
2: Emergency DC braking
0
Emergency DC braking time
0.0 20.0 (s)
1.0
DC braking current
0 100 (%)
30
(Example of terminal assignment): Assigning the trip stop function to the RST terminal
Title Function Adjustment range Setting
Input terminal selection (RST)
0 51
11
(External trip stop)
Notes:
1) Emergency stopping via the specified terminal is possible, even during panel operation.
2) If
is set to "2" (Emergency DC braking) and DC braking is not required for normal stopping, set
the DC braking time (
) to 0.0 (sec).