Toshiba VF-S9 Power Supply User Manual


 
E6580757
M-2
13
(Continued)
Error code
Communication
No.
Problem Possible causes Remedies
C Overvoltage during
constant-speed op-
eration
The input voltage fluctuates abnormally.
(1) The power supply has a capacity of
200kVA or more.
(2) A power factor improvement capacitor is
opened or closed.
(3) A system using a thyristor is connected
to the same power distribution line.
The motor is in a regenerative state be-
cause the load causes the motor to run at
a frequency higher than the inverter out-
put frequency.
Insert a suitable input reactor.
Install a dynamic braking resistor.
D Inverter overload
The acceleration time is too short.
The DC braking amount is too large.
The V/F setting is improper.
A restart signal is input to the rotating
motor after a momentary stop, etc.
The load is too large.
Increase the acceleration time .
Reduce the DC braking amount
and the DC braking time .
Check the V/F parameter setting.
Use (auto-restart) and
(ride-through control).
Use an inverter with a larger rating.
E Motor overload
The V/F setting is improper.
The motor is locked up.
Low-speed operation is performed con-
tinuously.
An excessive load is applied to the motor
during operation.
Check the V/F parameter setting.
Check the load (operated machine).
Adjust to the overload that the
motor can withstand during operation in a
low speed range.
* 9 Output phase failure
A phase failure occurred in the output line
of the main circuit.
Check the main circuit output line, motor,
etc., for phase failure.
Enable (Output phase failure de-
tection).
* 8 Input phase failure
A phase failure occurred in the input line
of the main circuit.
Check the main circuit input line for phase
failure.
Enable (input phase failure detec-
tion).
2Eh External thermal trip
A thermal trip command is entered from
an external input device.
Check the external input device.
* 20h Over-torque trip
The load torque rises up to the over-
torque detection level during operation
Enable (Over - torque trip selection)
Check whether the system is in a normal
condition.
F Dynamic braking re-
sistor overload trip
The deceleration time is too short.
The dynamic braking amount is too large.
Increase the deceleration time .
Use a dynamic resistor with a larger ca-
pacity (W) and adjust (PBR ca-
pacity parameter) accordingly.
10h Overheat
The cooling fan does not rotate.
The ambient temperature is too high.
The vent is blocked up.
A heat generating device is installed close
to the inverter.
The thermistor in the unit is broken.
Restart the operation by resetting the
inverter after it has cooled down enough.
The fan requires replacement if it does
not rotate during operation.
Secure sufficient space around the
inverter.
Do not place any heat-generating device
near the inverter.
Make a service call.
* 1E Undervoltage trip
(main circuit)
The input voltage (in the main circuit) is
too low.
Check the input voltage.
Enable (undervoltage trip selec-
tion).
To cope with a momentary stop due to
undervoltage, enable (ride-through
control) and (auto-restart).
* With a parameter, you can choose between trip-on and -off.
(Continued overleaf)