Reset of user-defined parameters (=)
Setting to returns all parameters to the settings saved by setting the parameter =.
* The above settings and allows you to have your own default parameter settings.
Cumulative fan operation time clear (=)
Setting to resets the cumulative fan operation time to the initial value (0 [zero] time). Set this parameter
when replacing the cooling fan, and so on.
Acceleration/deceleration time setting: 0.01 to 600.0 sec. (=)
When is set to , the acceleration/deceleration time can be set within a range of 0.01 to 600.0 sec.
Acceleration/deceleration time setting: 0.1 to 6000 sec. (=)
When is set to , the acceleration/deceleration time can be set within a range of 0.1 to 6000 sec.
500V-50Hz default setting (=)
Setting tocauses default value is to be set for 500V-50Hz.
When to be set after setting default value is to be set for 500V-50Hz (same value as )
Setting tocauses all the following parameters to be changed from factory shipment (setting)
• Base frequency 1 : 50Hz • AI2 input point 2 frequency : 50Hz
• Base frequency voltage 1 : 500V •
RP/high-speed pulse input point 2 frequency
: 50Hz
.• Upper limit frequency : 50Hz •
Automatic light-load high-speed operation frequency
: 50Hz
• VI/II input point 2 frequency : 50Hz •
Commercial power/inverter switching frequency
: 50Hz
• RR/S4 input point 2 frequency : 50Hz • PID deviation upper limit : 50Hz
• Base frequency 2 : 50Hz • PID deviation lower limit : 50Hz
• Base frequency voltage 2 : 500V • Process upper limit : 50Hz
• Base frequency 3 : 50Hz • PID output upper limit : 50Hz
• Base frequency voltage 3 : 500V • Forward speed limit input level : 50Hz
• Base frequency 4 : 50Hz • Reverse speed limit input level : 50Hz
• Base frequency voltage 4 : 500V • Undervoltage detection level : 66%
• RX input point 2 frequency : 50Hz • Overvoltage limit operation level :134%
• AI1 input point 2 frequency : 50Hz •
Regenerative power ride-through control
level: 75%
• Point 2 frequency : 50Hz
575V-60Hz default setting(=)
Setting tocauses default value is to be set for 575V-60Hz.
When to be set after setting default value is to be set for 575V-60Hz (same value as )
• Base frequency 1 : 60Hz • AI2 input point 2 frequency : 60Hz
• Base frequency voltage 1 : 575V •
RP/high-speed pulse input point 2 frequency
: 60Hz
.• Upper limit frequency : 60Hz •
Automatic light-load high-speed operation frequency
: 60Hz
• VI/II input point 2 frequency : 60Hz •
Commercial power/inverter switching frequency
: 60Hz
• RR/S4 input point 2 frequency : 60Hz • PID deviation upper limit : 60Hz
• Base frequency 2 : 60Hz • PID deviation lower limit : 60Hz
• Base frequency voltage 2 : 575V • Process upper limit : 60Hz
• Base frequency 3 : 60Hz • PID output upper limit : 60Hz
• Base frequency voltage 3 : 575V • Forward speed limit input level : 60Hz
• Base frequency 4 : 60Hz • Reverse speed limit input level : 60Hz
• Base frequency voltage 4 : 575V • Undervoltage detection level : 66%
• RX input point 2 frequency : 60Hz • Overvoltage limit operation level :113%
• AI1 input point 2 frequency : 60Hz •
Regenerative power ride-through control
level: 75%
• Point 2 frequency : 60Hz