Toshiba VF-AS1 Power Supply User Manual


 
E6581528
B-2
2
Caution
Prohibited
• Do not attach devices with built-in capacitors (such as noise filters or surge absorber) to the output
(motor side) terminal.
This could cause a fire.
Preventing radio noise
To prevent electrical interference such as radio noise, separately bundle wires to the main circuit's power terminals
(R/L1, S/L2, T/L3) and wires to the motor terminals (U/T1, V/T2, W/T3).
Control and main power supply
The control power supply and the main circuit power supply for the VF-AS1 are the same. If a malfunction or trip
causes the main circuit to be shut off, control power will also be shut off.
If you want to keep the control circuit alive when the main circuit shuts off due to trouble or tripping, you use a
transformer (down to 400V) and an optional control power supply backup unit (CPS002Z).
Wiring
• For ground terminal G/E use wires of the size that is equivalent to or larger than those given in table below and
always ground the inverter.
Use as large and short a ground wire as possible and wire it as close as possible to the inverter.
Applicable Motor Voltage
class
500V 600V 690V
Grounding wire size
(AWG) [Note]
Grounding wire size
(mm
2
) [Note]
VFAS1-5015PM 1.5kW
2HP
14 2.5
VFAS1-5022PM 2.2kW 3HP 14 2.5
VFAS1-5030PM 3.0kW
-
- 2.5
VFAS1-5040PM 4kW
5HP
14 2.5
VFAS1-5055PM 5.5kW
7.5HP
14 2.5
VFAS1-5075PM 7.5kW
10HP
12 4
VFAS1-6022PL 1.5kW 2HP 2.2kW - 2.5
VFAS1-6030PL 2.2kW
3HP
3kW - 2.5
VFAS1-6055PL 4kW
5HP
5.5kW - 2.5
VFAS1-6075PL 5.5kW
7.5HP
7.5kW - 2.5
VFAS1-6110PL 7.5kW
10HP
11kW - 4
VFAS1-6150PL 11kW
15HP
15kW 10 6
VFAS1-6185PL 15kW
20HP
18.5kW 10 10
VFAS1-6220PL 18.5kW
25HP
22kW 10 10
VFAS1-6300PL 22kW
30HP
30kW 10 10
VFAS1-6370PL 30kW
40HP
37kW 8 16
VFAS1-6450PL 37kW
50HP
45kW 8 16
VFAS1-6550PL 45kW
60HP
55kW 8 16
VFAS1-6750PL 55kW
75HP
75kW 6 25
VFAS1-6900PL 75kW
100HP
90kW 6 35
VFAS1-6110KPC 90kW
125HP
110kW 6 35
VFAS1-6132KPC 110kW
150HP
132kW 2 50
VFAS1-6160KPC 132kW
-
160kW - 70
VFAS1-6200KPC 160kW
200HP
200kW 2 95
VFAS1-6250KPC 185kW
250HP
250kW 1 150
VFAS1-6315KPC 250kW
350HP
315kW 2/0 150
VFAS1-6400KPC 315kW
450HP
400kW 3/0 185
VFAS1-6500KPC 400kW
550HP
500kW 4/0 150x2
VFAS1-6630KPC 500kW
700HP
630kW 4/0 185x2
Note1: The recommended cable size is that of the cable (e.g. 1500V class cupper cable) with continuous maximum
permissible temperature of 75°C. Ambient temperature is 40°C or less and the wiring distance is 30m or less.