Toshiba VF-AS1 Power Supply User Manual


 
K-31
E6581528
11
[28] Communication function [3/4] Sensorless vector/vector with sensor (:Effective, -:Ineffective)
Default setting
Vector control
Title
Commun
ication
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)

=
500V
-50Hz

=
575V
-60Hz

=
690V
-50Hz
Write
during
running
Speed
control
Torque
control
V/f
Constant
Reference
 0845
Communication option
(DeviceNet/ PROFIBUS) setting
12
0000~ 1/1 0000 0000 0000 Enabled / / *1
 0846
Communication option
(DeviceNet/ PROFIBUS) setting
13
0000~ 1/1 0000 0000 0000 Enabled / / *1
 0850
Disconnection detection
extended time
0.0~100.0 sec. 0.1/0.1 0.0 0.0 0.0 Enabled / / *1
 0851
Inverter operation at
disconnection
0:Inverter stop, communication command,
frequency mode open (by , )
1:None (continued operation)
2:Deceleration stop
3:Coast stop
4:Network error ( trip)
5:Preset speed operation (by  setting)
1/1 0 0 0 Enabled / / *1
 0852
Preset speed operation
selection
0:None
1~15:Preset speed operation (by parameter
setting)
1/1 0 0 0 Enabled / / *1
 0853
Communication option station
address monitor
0~255 1/1 0 0 0 Enabled / / *2
 0854
Communication option speed
switch monitor
DeviceNet/CC-Link
0~255 1/1 0 0 0 Enabled / / *2
 0870 Block write data 1
0:Disabled
1:Command information 1
2:Command information 2
3:Frequency command
4:Terminal board output data
5:Communication analog data
1/1 0 0 0 Enabled / / 6. 39. 1
 0871 Block write data 2 Ditto 1/1 0 0 0 Enabled / / 6. 39. 1
*1: For details, refer to Instruction Manual (E6581281, E6581343) specified in Section 6.42.
*2: For details, refer to Instruction Manual (E6581281, E6581343, E6581288) specified in Section 6.42.