Toshiba VF-AS1 Power Supply User Manual


 
E6581528
E-14
5
Base frequency
voltage 1 
Output voltage
[V]/[%]
Output frequency [Hz]


Base frequency 1
0






VF1
VF2
VF3
VF4
VF5
V/f 5-point setting
Note 1: Restrict the amount of torque to boost () to 3% or so. Boosting the torque too much may impair the
linearity between points.
Note 2: If the V/f 5-point is set within the diagonally shaded area in the figure below, the V/f 5-point is placed
automatically on the boundary line (heavy line in the figure).
: Area in which the
V/f 5-point cannot
be set
Voltage
Frequency
0
×
0.4413
100%

6) Operating the motor at periodic speeds by means of a motor speed
sensor
Setting for V/f control mode selection = (PG feedback control)
Set  to to operate the motor at periodic speeds.
A PG feedback device (optional) is needed. In addition, a motor with a speed sensor (encoder) should be used.
Use this setting when operating a motor two or more ranks lower in capacity than the inverter at periodic speeds.
Note that the accuracy obtained by = is lower than that obtained by setting  to . Also,  should be set
to to perform torque control.  cannot be set to in such a case.
Output torque decreases considerably in regenerative low speed operation (motor slip frequency or less). Set  to
if regenerative low speed torque is necessary.
Motor constant must be set.
The motor constant can be set in any of the following two ways:
1) Automatic setting
Enter the following information that is indicated on the motor nameplate, and then execute the auto-tuning 1
command (Set  to , and then reset  to .).
<Information indicated on motor nameplate>
 (Base frequency),  (Base frequency voltage),  (Motor rated capacity),  (Motor rated
current), (Motor rated rotational speed) Refer to 6.22 selection 1.
2) Manual setting
Set each motor constant manually. Refer to 6.22 selection 2.