K-29
E6581528
11
[28] Communication function [1/4] Sensorless vector/vector with sensor (●:Effective, -:Ineffective)
Default setting
Vector control
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
=
500V
-50Hz
=
575V
-60Hz
=
690V
-50Hz
Write
during
running
Speed
control
Torque
control
V/f
Constant
Reference
0781
Quick registration parameter
31
0~999 *1 1/1 999 999 999 Enabled ●/● ●/● ● 5. 22
0782
Quick registration parameter
32
0~999 *1 1/1
50
(PSEL)
50
(PSEL)
50
(PSEL)
Enabled ●/● ●/● ● 5. 22
0800
Communication speed (2-wire
RS485)
0:9600 bps
1:19200 bps
2:38400 bps
1/1 1 1 1 Enabled ●/● ●/● ● 6. 39. 1
0801
Parity (common to 2-wire
RS485 and 4-wire RS485)
0:Non parity
1:Even parity,
2:Odd parity
1/1 1 1 1 Enabled ●/● ●/● ● 6. 39. 1
0802 Inverter number (common) 0~247 1/1 0 0 0 Enabled ●/● ●/● ● 6. 39. 1
0803
Communications time-out time
(common to 2-wire RS485 and
4-wire RS485)
0:OFF, 1~100 sec. 1/1 0 0 0 Enabled ●/● ●/● ● 6. 39. 1
0804
Communications time-out
action (common to 2-wire
RS485 and 4-wire RS485)
0~8 1/1 8 8 8 Enabled ●/● ●/● ● 6. 39. 1
0805
Send waiting time (2-wire
RS485)
0.00:Default, 0.01~2.00 sec. 0.01/0.01 0.00 0.00 0.00 Enabled ●/● ●/● ● 6. 39. 1
0806
Master/slave setting for
inverter-to-inverter
communications (2-wire
RS485)
0:Slave (issues a 0Hz command if something
goes wrong with the master)
1:Slave (continues operation if something goes
wrong with the master)
2:Slave (trips for emergency stop if something
goes wrong with the master)
3:Master (sends a frequency command)
4:Master (sends an output frequency)
5.Master (sends a torque command)
6.Master (sends an output torque command)
1/1 0 0 0 Enabled ●/● ●/● ● 6. 39. 1
0807
Protocol selection (2-wire
RS485)
0:TOSHIBA
1:MODBUS
1/1 0 0 0 Enabled ●/● ●/● ● 6. 39. 1
0810 Frequency point selection
0:Disabled
1:2-wire RS485
2:4-wire RS485
3:Communication add option
1/1 0 0 0 Enabled ●/● - ● 6. 39. 1
0811 Point 1 setting 0-100% 1/1 0 0 0
Enabled*1
●/● - ● 6. 39. 1
0812 Point 1 frequency 0.0~ Hz 0.1/0.01 0.0 0.0 0.0
Enabled*1
●/● - ● 6. 39. 1
0813 Point 2 setting 0~100% 1/1 100 100 100
Enabled*1
●/● - ● 6. 39. 1
0814 Point 2 frequency 0.0~ Hz 0.1/0.01 50.0 60.0 50.0
Enabled*1
●/● - ● 6. 39. 1
0820
Communication speed (4-wire
RS485)
0:9600 bps
1:19200 bps
2:38400 bps
1/1 1 1 1 Enabled ●/● ●/● ● 6. 39. 1
0825
Send waiting time (4-wire
RS485)
0.00:Default, 0.01~2.00 sec. 0.01/0.01 0.00 0.00 0.00 Enabled ●/● ●/● ● 6. 39. 1
*1: Effective when a command value is sent by communication.