Toshiba VF-AS1 Power Supply User Manual


 
E6581528
E-45
5
690V-50Hz default setting(=)
Setting  tocauses default value is to be set for 690V-50Hz.
When  to be set after setting default value is to be set for 690V-50Hz (same value as )
Setting  tocauses all the following parameters to be changed from factory shipment (setting)
Base frequency 1  : 50Hz
RP/high-speed pulse input point 2 frequency
 : 50Hz
Base frequency voltage 1  : 690V
Automatic light-load high-speed operation frequency
 : 50Hz
.• Upper limit frequency  : 50Hz
Commercial power/inverter switching frequency
 : 50Hz
• VI/II input point 2 frequency  : 50Hz • PID deviation upper limit  : 50Hz
• RR/S4 input point 2 frequency  : 50Hz • PID deviation lower limit  : 50Hz
Base frequency 2  : 50Hz • Process upper limit  : 50Hz
Base frequency voltage 2  : 690V • PID output upper limit  : 50Hz
• Base frequency 3  : 50Hz • Forward speed limit input level  : 50Hz
Base frequency voltage 2  : 690V • Reverse speed limit input level  : 50Hz
• Base frequency 4  : 50Hz
Undervoltage detection
level  : 59%
Base frequency voltage 4  : 690V
Overvoltage limit operation
level  :113%
• RX input point 2 frequency  : 50Hz
Regenerative power ride-through control
level: 75%
• AI1 input point 2 frequency  : 50Hz • Point 2 frequency  : 50Hz
• AI2 input point 2 frequency  : 50Hz