Toshiba VF-AS1 Power Supply User Manual


 
E6581528
A-28
1
Calorific values of the inverter and the required ventilation
The energy loss when the inverter converts power from AC to DC and then back to AC is typically about 2.5% to 5%.
In order to suppress the rise in temperature inside the cabinet when this loss becomes heat loss, the interior of the
cabinet must be ventilated and cooled.
The amount of forced air-cooling ventilation required and the necessary heat exchange surface area when operating
in a sealed cabinet according to motor capacity are as follows.
Applicable Motor
Voltage
class
500V 600V 690V
Calorific
values
(W)
Amount of forced air cooling
ventilation required
(m
3
/min)
Heat exchange surface area
required for sealed storage
cabinet
(m
2
)
VFAS1-5015PM 1.5kW 2HP 84 0.48 1.7
VFAS1-5022PM 2.2kW
3HP
100 0.57 2.0
VFAS1-5030PM 3kW
-
118 0.68 2.4
VFAS1-5040PM 4kW
5HP
143 0.82 2.9
VFAS1-5055PM 5.5kW
7.5HP
183 1.1 3.7
VFAS1-5075PM 7.5kW
10HP
244 1.4 4.9
VFAS1-6022PL 1.5kW 2HP 2.2kW 111 0.64 2.3
VFAS1-6030PL 2.2kW
3HP
3kW 119 0.68 2.4
VFAS1-6055PL 4kW
5HP
5.5kW 158 0.91 3.2
VFAS1-6075PL 5.5kW
7.5HP
7.5kW 182 1.1 3.7
VFAS1-6110PL 7.5kW
10HP
11kW 227 1.3 4.6
VFAS1-6150PL 11kW
15HP
15kW 300 1.8 6.0
VFAS1-6185PL 15kW
20HP
18.5kW 386 2.3 7.8
VFAS1-6220PL 18.5kW
25HP
22kW 463 2.7 9.3
VFAS1-6300PL 22kW
30HP
30kW 556 3.2 11.2
VFAS1-6370PL 30kW
40HP
37kW 716 4.1 14.4
VFAS1-6450PL 37kW
50HP
45kW 911 5.2 18.3
VFAS1-6550PL 45kW
60HP
55kW 1087 6.2 21.8
VFAS1-6750PL 55kW
75HP
75kW 1545 8.9 30.9
VFAS1-6900PL 75kW
100HP
90kW 1947 11.1 39.0
VFAS1-6110KPC 90kW
125HP
110kW 2320
13.3 46.4
VFAS1-6132KPC 110kW
150HP
132kW 2740
15.7 54.8
VFAS1-6160KPC 132kW
-
160kW 3270
18.7 65.4
VFAS1-6200KPC 160kW
200HP
200kW 4010
22.9 80.2
VFAS1-6250KPC 185kW
250HP
250kW 5140
29.3 103
VFAS1-6315KPC 250kW
350HP
315kW 6290
35.9 126
VFAS1-6400KPC 315kW
450HP
400kW 7600
43.4 152
VFAS1-6500KPC 400kW
550HP
500kW 9610
54.8 193
VFAS1-6630KPC 500kW
700HP
630kW 11920
68.0 239
Note1: The heat loss for the external options (input reactor, radio noise reduction filters, etc.) is not included in the
calorific values in the table.
Note2: Each calorific value in the table refers to the quantity of heat that an inverter produces when it is operated
continuously at the factory default  (carrier frequency) under a load factor of 100%.