Toshiba VF-AS1 Power Supply User Manual


 
E6581528
G-13
7
7.3.3 Setup by analog input signals (RX terminal)
Connect voltage signal (0 to ±10Vdc) to the terminal RX so that the inverter can be run and stopped with external
commands.
Title Function Adjustment range Default setting Example of setting
 Command mode selection ~ (Terminal) (Terminal)

Frequency setting mode
selection 1
~ (RR/S4) (RX)
 FM terminal meter selection ~  
 FM terminal meter adjustment - - -
 Frequency priority selection ,
 Analog input filter (No filter)~ (Max. filter)  
 RX input point 1 setting -~ %  
 RX input point 1 frequency ~ Hz  
 RX input point 2 setting -~ %  
 RX input point 2 frequency ~ Hz(Note 1)(Note 1)
Note 1: Refer to page K-9.
Run/stop setup
Run/stop operation by means of external
commands.
Setup of frequency setting signal and
running frequency characteristic
To set up frequency setting signal to be
input to the external signal (RX terminal)
and characteristic of running frequency.
Frequency characteristic is set up at the
two points of RX reference point 1
(

)/frequency (

), RX
reference point 2 (

)/frequency
(

).
Connection and calibration of
frequency meter
Connect a 1mAdc full-scale DC current
meter, 7.5Vdc full-scale DC voltmeter or
rectifier type AC voltmeter.
For calibration of the meter, refer to the
Section 5.16.
Run/Sto
p
-10~+10Vdc
%




Point 2
Point 1
Frequenc
y
settin
g
si
g
nal
 
-100%
    
0%
    
100%
(-10V
  
~
 
0V
 
~
 
+10V)
Operation frequency Hz
Forward
run
Reverse
run
*: Regardless of open/closed circuit between R and CC terminals, run and stop operation is
controllable.
Switching between forward run and reverse run is controllable by the terminals F/R and RX
if reverse run prohibition selection  is properly set up.
For details, refer to Section 6.14.4.
Motor
R/L1
U/T1
MCCB
Power
supply
S/L2
T/L3
V/T2
W/T3
CCA RX
RES
S1
S2
CC
S3
F
R
FM
AM
FLA
FLB
FLC
P24/PLC
PWR
OUT1
VI/II
PP
VF-AS1
CHARGE
Frequency
meter
NO
CC
RR/S4
IM
OUT2