Toshiba VF-AS1 Power Supply User Manual


 
K-11
E6581528
11
[10] Jump frequency Sensorless vector/vector with sensor (:Effective, -:Ineffective)
Default setting
Vector control
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)

=
500V
-50Hz

=
575V
-60Hz

=
690V
-50Hz
Write
during
running
Speed
control
Torque
control
V/f
Constant
Reference
 0270 Jump frequency 1 0.0~ Hz 0.1/0.01 0.0 0.0 0.0 Enabled / - 6. 12
 0271 Jumping width 1 0.0~30.0Hz 0.1/0.01 0.0 0.0 0.0 Enabled / - 6. 12
 0272 Jump frequency 2 0.0~ Hz 0.1/0.01 0.0 0.0 0.0 Enabled / - 6. 12
 0273 Jumping width 2 0.0~30.0Hz 0.1/0.01 0.0 0.0 0.0 Enabled / - 6. 12
 0274 Jump frequency 3 0.0~ Hz 0.1/0.01 0.0 0.0 0.0 Enabled / - 6. 12
 0275 Jumping width 3 0.0~30.0Hz 0.1/0.01 0.0 0.0 0.0 Enabled / - 6. 12
[11] Preset speed operation frequency (8~15) Sensorless vector/vector with sensor (:Effective, -:Ineffective)
Default setting
Vector control
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)

=
500V
-50Hz

=
575V
-60Hz

=
690V
-50Hz
Write
during
running
Speed
control
Torque
control
V/f
Constant
Reference
 0287
Preset speed operation
frequency 8
~ Hz 0.1/0.01 0.0 0.0 0.0 Enabled / - 5. 12
 0288
Preset speed operation
frequency 9
~ Hz 0.1/0.01 0.0 0.0 0.0 Enabled / - 5. 12
 0289
Preset speed operation
frequency 10
~ Hz 0.1/0.01 0.0 0.0 0.0 Enabled / - 5. 12
 0290
Preset speed operation
frequency 11
~ Hz 0.1/0.01 0.0 0.0 0.0 Enabled / - 5. 12
 0291
Preset speed operation
frequency 12
~ Hz 0.1/0.01 0.0 0.0 0.0 Enabled / - 5. 12
 0292
Preset speed operation
frequency 13
~ Hz 0.1/0.01 0.0 0.0 0.0 Enabled / - 5. 12
 0293
Preset speed operation
frequency 14
~ Hz 0.1/0.01 0.0 0.0 0.0 Enabled / - 5. 12
 0294
Preset speed operation
frequency 15
(Forced operation frequency)
~ Hz 0.1/0.01 0.0 0.0 0.0 Enabled / - 5. 12
[12] Tripless intensification setup [1/2] Sensorless vector/vector with sensor (:Effective, -:Ineffective)
Default setting
Vector control
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)

=
500V
-50Hz

=
575V
-60Hz

=
690V
-50Hz
Write
during
running
Speed
control
Torque
control
V/f
Constant
Reference
 0300 PWM carrier frequency 1.0~16.0kHz (2.5~8.0kHz) *1 0.1/0.1 *2 *2 *2 Enabled / / 5. 17
 0301 Auto-restart control selection
0:Disabled, 1:At auto-restart
2:When turning ST operation standby signal on
or off, 3:1+2, 4:Starting
1/1 0 0 0 Disabled / / 5. 18.1
 0302
Regenerative power
ride-through control
0:Disabled, 1:Power ride-through
2:Deceleration stop during power failure
3:Synchronized deceleration/acceleration
(synchronized acceleration/deceleration
signal)
4:Synchronized deceleration/acceleration
(synchronized acceleration/deceleration signal+power
failure)
1/1 0 0 0 Disabled / -/- 5. 18. 2
 0303 Retry selection 0:Deselect, 1-10 times 1/1 0 0 0 Enabled / / 6. 14. 1
This parameter moves to a fundamental parameter. *1: For 200V-55/75kW models and 400V-90kW to 400V-280kW models, the carrier frequency is between 2.5 and 8.0kHz inclusive.
*2: Default values vary depending on the capacity. See the table of K-46.