K-41
E6581528
11
[Input terminal function setting (1/2)] Sensorless vector/vector with sensor (●: valid, -: invalid)
Positive
logic
Negative
logic
Function
Speed
control
Tor qu e
control
V/f = = Reference
0 1 No function is assigned ●/● ●/● ● - -
2 3 F: Forward run command ●/● ●/● ● ● -
4 5 R: Reverse run command ●/● ●/● ● ● -
6 7 ST: Standby ●/● ●/● ● *1 -
8 9 RES: Reset ●/● ●/● ● *2 -
10 11 S1: Preset speed 1 ●/● - ● ● -
12 13 S2: Preset speed 2 ●/● - ● ● -
14 15 S3: Preset speed 3 ●/● - ● ● -
16 17 S4: Preset speed 4 ●/● - ● ● -
18 19 Jog run ●/● - ● ● ●
20 21 Emergency stop ●/● ●/● ● *2 -
22 23 DC braking ●/● - ● ● ●
24 25 Acceleration/deceleration switching 1 ●/● - ● ● -
26 27 Acceleration/deceleration switching 2 ●/● - ● ● -
28 29 V/f switching signal 1 ●/● - ● ● -
30 31 V/f switching signal 2 ●/● - ● ● -
32 33 Torque limit switching signal 1 ●/● ●/● ● ● -
34 35 Torque limit switching signal 2 ●/● ●/● ● ● -
36 37 PID control OFF selection ●/● - ● ● -
38 39 Pattern operation selection 1 ●/● - ● ● -
40 41 Pattern operation selection 2 ●/● - ● ● -
42 43 Pattern operation continuation signal ●/● - ● ● -
44 45 Pattern operation trigger signal ●/● - ● ● -
46 47 External thermal error ●/● - ● ● -
48 49 Communication priority cancel ●/● - ● ● -
50 51
Holding of HD operation (stop of three-wire
operation)
●/● - ● ● -
52 53 PID differentiation/integration reset ●/● - ● ● -
54 55 PID forward/reverse switching ●/● - ● ● -
56 57 Forced continuous operation ●/● - ● ● -
58 59 Specified speed operation ●/● - ● ● -
60 61 Acceleration/deceleration suspend signal ●/● - ● ● -
62 63 Power failure synchronized signal ●/● - ● ● -
64 65 My function RUN signal ●/● ●/● ● ● -
66 67 Auto-tuning signal ●/● - ● ● -
68 69 Speed gain switching ●/● - ● ● -
7.2.1
*1: Valid any time
*2: Independent of , and all command are valid.