E6581528
F-72
6
6.36.4 Changing the standard monitor display
: Standard monitor display selection
~ : Status monitor 1~8 display selection
These parameters are used to select the item to be displayed when the power turned on and also to change items
displayed in status monitor mode.
⇒ For details, refer to Section 8.3.
6.36.5 Canceling the operation command
: Operation command clear selection when input terminal function ST
( Refer to section 7.2.1) is OFF
•
Function
You can use this function when driving with the RUN key on the operation panel.
When it turns on again after turning off the input terminal which assigned the standby ”ST” function(Refer to
7.2.1) during driving the inverter, the inverter will drive again without pushing the RUN key.
Using this function, the inverter is not driven again unless the RUN key is pushed on after turning on the ST
signal.
Title Function Adjustment range Default setting
Operation command clear selection
when standby terminal (ST) is OFF
:Clear operation command
:Retain operation command
6.36.6 Selection of operation panel stop pattern
: Operation panel stop pattern selection
•
Function
This parameter are used to select a mode in which the motor started by pressing the
RUN
key on the
operation panel is stopped when the
STOP
key is pressed.
1) Deceleration stop
The motor stops in the deceleration time set with the parameter (or , ).
2) Coast stop
The output of the inverter is cut off. The motor comes to a stop after coasting for a while by inertia. Depending on
the load, the motor may keep running for a good long time.
[Parameter setting]
Title Function Adjustment range Default setting
Operation panel stop pattern selection
:Deceleration stop
:Coast stop
6.36.7 Setting of a torque command in panel operation mode
: Operation panel torque command (reference value in %)
• Function
This parameter allows you to set a torque command value when torque is controlled with the operation panel.
Note: This parameter is operative only when , , and are set to . The value set
with this
p
arameter is used as the command value
(
%
)
for each function.
Operation panel operation: Torque command selection is set at (Panel input).
[Parameter setting]
Title Function Adjustment range Default setting
Operation panel torque command -~ %
⇒ For details, refer to Instruction Manual (E6581331) specified in Section 6.42.