E6581528
A-1
1
1. Read first
1.1 Check the product
Before using the product you have purchased, check to make sure that it is exactly what you ordered.
Caution
Mandatory
Use an inverter that conforms to the specifications of the power supply and three-phase induction
motor being used. If the inverter being used does not conform to those specifications, not only will
the three-phase induction motor not rotate correctly, but it may cause serious accidents through
overheating and fire.
Type indication
label
Series name
Power supply
Motor capacity
Inverter Type
Applicable motor
Invert rated output capacity
Power supply
Related input current
Related output current
Serial No.
Type indication Inverter main unit
Carton box
Name plate
Warning label
VF-AS1
3PH-500/600/690V
11kW/15HP/15kW
Type indication
Name plate
Warning label
Instruction manual
This manual
Risk of injury, electric shock or fire.
・
Read the Instruction Manual.
・
Do not open the cover while power is applied or
for 15 minutes after power has been removed.
・
Ensure proper eart h connect ion.
DANGER
1. 2 Contents of the product code
Explanation of the type and form written on the label.
Type Form
V F A S 1 -
6 1 5 0 P L Y - WN - A 2 2
Model name
TOSVERT
VF-AS1 series
Operation panel
P: Provided
Additional functions II
Y: Others
(non-standard)
Applicable motor capacity
for 690V Power supply
022:2.2kW
030:3.0kW
055:5.5kW
075:7.5kW
110:11kW
150:15kW
185:18.5kW
220:22kW
300:30kW
370:37kW
450:45kW
550:55kW
750:75kW
900:90kW
110K:110kW
132K:132kW
160K:160kW
200K:200kW
250K:250kW
315K:315kW
400K:400kW
500K:500kW
630K:630kW
Voltage class
5: 500V~600V
6: 500V~690V
Special
specification code
A
: Special
specification code
(
is a number)
Additional functions I
L: Built-in EMC filter
+
basic filter
M: Built-in basic filter
C: Built-in EMC filter
S
p
ecial s
p
ecification code
Default interface logic
WN: Negative
HN: US Negative
*1)
*1): Applicable motor capacity changes with power supply. ⇒ For more details, refer to Section 1.3 or Section 12.