Toshiba VF-AS1 Power Supply User Manual


 
E6581528
11
K-22
[23] Pattern operation [3/3] Sensorless vector/vector with sensor (:Effective, -:Ineffective)
Default setting
Vector control
Title
Commun
ication
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)

=
500V
-50Hz

=
575V
-60Hz

=
690V
-50Hz
Write
during
running
Speed
control
Torque
control
V/f
Constant
Reference
 0573
Preset speed operation
frequency 13 operation mode
Ditto 1/1 0 0 0 Disabled / - 5. 12
 0574
Preset speed operation
frequency 14 operation mode
Ditto 1/1 0 0 0 Disabled / - 5. 12
 0575
Preset speed operation
frequency 15 operation mode
Ditto 1/1 0 0 0 Disabled / - 5. 12
[24] Protection functions [1/3] Sensorless vector/vector with sensor (:Effective, -:Ineffective)
Default setting
Vector control
Title
Commun
ication
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)

=
500V
-50Hz

=
575V
-60Hz

=
690V
-50Hz
Write
during
running
Speed
control
Torque
control
V/f
Constant
Reference
 0601 Stall prevention level 10~164%, 165:Deactivated 1/1 150 150 150 Enabled / - 6. 33. 1
 0602
Inverter trip record retention
selection
0:Clear when power is turned off
1:Retain even after power is turned off
1/1 0 0 0 Enabled / / 6. 33. 2
 0603 Emergency stop
0:Coast stop
1:Deceleration stop
2:Emergency DC braking
3:Deceleration stop (deceleration 4)
1/1 0 0 0 Disabled / / 6. 33. 3
 0604
Emergency DC braking control
time
0.0~20.0 sec. 0.1/0.1 1.0 1.0 1.0 Enabled / / 6. 33. 3
 0605
Output phase failure detection
mode selection
0:Deselect
1:At starting (only one time after power is
turned on)
2:At starting (each time power is turned on)
3:During operation
4:At starting + during operation
5:Output cut-off detection enabled
1/1 0 0 0 Disabled / / 6. 33. 4
 0606 OL reduction starting frequency 0.0~60.0Hz 0.1/0.01 6.0 6.0 6.0 Enabled / / 5. 14
 0607 Motor 150%-overload time limit 10~2400 sec. 1/1 300 300 300 Enabled / / 5. 14
 0608
Input phase failure detection
mode selection
0:Disabled
1:Enabled
1/1 1 1 1 Disabled / / 6. 33. 7
 0609
Low current detection
hysteresis width
1~20% 1/1 10 10 10 Enabled / / 6. 33. 8
 0610 Low current trip selection
0:No trip
1:Trip
1/1 0 0 0 Enabled / / 6. 33. 8
 0611 Low current detection current 0~100% 1/1 0 0 0 Enabled / / 6. 33. 8
 0612 Low current detection time 0~255 sec. 1/1 0 0 0 Enabled / / 6. 33. 8
 0613
Selection of short circuit
detection at starting
0:Each time (standard pulse)
1:Only one time after power is turned on
2:Each time (short pulse)
3.Only one time after power is turn on (short
pulse)
4:Each time (Extremely shot-time pulse)
5.Only one time after power is turn on
(Extremely shot-time pulse)
1/1 0 0 0 Disabled / / 6. 33. 9