Toshiba VF-AS1 Power Supply User Manual


 
K-23
E6581528
11
[24] Protection functions [2/3] Sensorless vector/vector with sensor (:Effective, -:Ineffective)
Default setting
Vector control
Title
Commun
ication
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)

=
500V
-50Hz

=
575V
-60Hz

=
690V
-50Hz
Write
during
running
Speed
control
Torque
control
V/f
Constant
Reference
 0615 Overtorque trip selection
0:No trip
1:Trip
1/1 0 0 0 Enabled / / 6. 33. 10
 0616
Overtorque detection level
during power running
0~250% 1/0.01 150 150 150 Enabled / / 6. 33. 10
 0617
Overtorque detection level
during regenerative braking
0~250% 1/0.01 150 150 150 Enabled / / 6. 33. 10
 0618 Overtorque detection time 0.00~10.00 sec. 0.01/0.01 0.50 0.50 0.50 Enabled / / 6. 33. 10
 0619
Overtorque detection
hysteresis
0~100% 1/0.01 10 10 10 Enabled / / 6. 33. 10
 0620 Cooling fan control selection
0:Auto
1:Always ON
1/1 0 0 0 Enabled / / 6. 33. 11
 0621
Cumulative operation time
alarm setting
0.1~999.9 (x100h) 0.1/0.1 610.0 610.0 610.0 Enabled / / 6. 33. 12
 0622
Abnormal speed detection
time
0.01~100.0 sec. 0.01/0.01 0.01 0.01 0.01 Enabled -/ / - 6. 33. 13
 0623
Overspeed detection
frequency upper band
0.0:Disabled, 0.1~30.0Hz 0.1/0.01 0.0 0.0 0.0 Enabled -/ / - 6. 33. 13
 0624
Overspeed detection
frequency lower band
0.0:Disabled, 0.1~30.0Hz 0.1/0.01 0.0 0.0 0.0 Enabled -/ / - 6. 33. 13
 0625 Undervoltage detection level
50~79% for 500V class
44~70% for 575V class
37~59% for 690V class, 80: (auto mode)
1/1
66 66 59 Disabled / / 6. 33. 15
 0626
Overvoltage limit operation
level
100~150%
1/1
134 134 113 Disabled / - 6. 14. 2
 0627 Undervoltage trip selection
0:Disabled
1:Enabled
1/1 0 0 0 Disabled / / 6. 33. 15
 0628
Undervoltage (trip alarm)
detection time
0.01~10.00 sec. 0.01/0.01 0.03 0.03 0.03 Disabled / / 6. 33. 15
 0629
Regenerative power ride-through
control
level
55~100% for 500V class
49~100% for 575V class
42~100% for 690V class
1/1 55 49 42 Disabled / / 6. 33. 16
 0630 Braking answer waiting time 0.0:Disabled, 0.1~10.0 sec. 0.1/0.1 0.0 0.0 0.0 Enabled / - - 6. 33. 17
 0631 Temperature detection
0:Standard (150%-60 sec.)
1:Estimation of temperature
1/1 0 0 0 Disabled - - - 5. 14
 0633
VI/II analog input wire
breakage detection level
0:None
1~100%
1/1 0 0 0 Enabled / / 6. 33. 18
 0634
Annual average ambient
temperature (calculation for
part replacement alarms)
1:-10~+10°C
2:+11~+20°C
3:+21~+30°C
4:+31~+40°C
5:+41~+50°C
6:+51~+60°C
1/1 3 3 3 Enabled / / 6. 33. 19
 0635
Rush current suppression
relay activation time
0.0~2.5 sec. 0.1/0.1 0.0 0.0 0.0 Disabled / / 6. 33. 20