E6581528
A-13
1
VFAS1-6110KPC models and larger: Grounding capacitor switching screw
«VFAS1-6110KPC~6160KPC, VFAS1-6400KPC~6630KPC»
To change the capacitance from
Small to Large, fix to part A shown
in the figure on the left with the
grounding capacitor switching
screw.
(Factory default position)
To change the capacitance from
Large to Small, fix to part B shown
in the figure on the left with the
grounding capacitor switching
screw.
A
B
A
B
Large
Small
Large
Small
*1: For VFAS1-6400KPC to 6630KPC
models, there are two places.
⇒ For details, refer to Section 1.4.1.
*1
«VFAS1-6200KPC~6315KPC»
To change the capacitance from
Small to Large, fix to part A shown
in the figure on the left with the
grounding capacitor switching
screw.
(Factory default position)
To change the capacitance from
Large to Small, fix to part B shown
in the figure on the left with the
grounding capacitor switching
screw.
A
B
Large Small
Large Small
Warning
Prohibited
In case of one phase grounding system (A three-phase supply power is connected in delta),
do not change the connection of grounding capacitor before factory setting. If connection
changed (this means the capacitance is increased), the capacitor may become damaged.
Note: If a neutral grounding system is used, changing the connection of the grounding capacitor as shown in the
figure at the top (changing the capacitance from Small to Large) makes the inverter compliant with the EMC
directive.