E6581528
L-2
12
2) Standard specifications (Power supply is based on 600V)
Item Specification
Voltage class
575V class
Applicable motor (HP)
2 3 5 7.5 10 15 20 25 30 40 50 60 75 100
Type VFAS1-
Form
5015PM 5022PM 5040PM 5055PM 5075PM 6150PL 6185PL 6220PL 6300PL 6370PL 6450PL 6550PL 6750PL 6900PL
Output capacity (kVA)
[Note 1]
2.9 4.1 6.4 9.4 12 18 23 29 34 43 54 65 80 103
Output current(A)
[Note 2]
2.7 3.9 6.1 9.0 11 17 22 27 32 41 52 62 77 99
Output voltage
Three-phase 500V~600V
(The maximum output voltage is equal
to the input supply voltage.)
Three-phase 500V~690V (The maximum output voltage is equal
to the input supply voltage.)
Rating
Overload current
rating
150%-1 minute, 165%-2 sec.
Dynamic braking
circuit
Built-in dynamic braking drive circuit
Electrical
brakin
g
Dynamic braking
resistor
An external braking resistor (option)
⇒ Rating: Refer to 5.19.
Voltage-frequency
Three-phase 500~600V-50/60Hz [Note 3] Three-phase 500~690V-50/60Hz [Note 3]
Power
su
pp
l
y
Allowable
fluctuation
Voltage + 10% - 15% [Note 4] Frequency ±5%
Protective method IP20 Enclosed type
Cooling method Forced air-cooled
Cooling fan noise (dBA)
60
64
Color RAL7016
EMC filter
Basic filter (Not complies with the European
EMC Directive)
Built-in
Reactor External AC reactor (option) Built-in DC reactor
Item Specification
Voltage class
575V class
Applicable motor (HP)
125 150 200 250 350 450 550 700
Type VFAS1-
Form
6110KPC 6132KPC 6200KPC 6250KPC 6315KPC 6400KPC 6500KPC 6630KPC
Output capacity (kVA)
[Note 1]
130 150 200 252 349 428 549 698
Output current(A)
[Note 2]
125 144 192 242 336 412 528 672
Output voltage Three-phase 500V~690V (The maximum output voltage is equal to the input supply voltage.)
Rating
Overload current
rating
150%-1 minute, 165%-2 sec.
Dynamic braking
circuit
Built-in dynamic braking drive
circuit
External dynamic braking circuit(option)
Electrical
brakin
g
Dynamic braking
resistor
An external braking resistor (option)
⇒ Rating: Refer to 5.19.
Voltage-frequency
Three-phase 500~690V-50/60Hz [Note 3]
Power
su
pp
l
y
Allowable
fluctuation
Voltage + 10% - 15% [Note 4] Frequency ±5%
Protective method IP00 Open type [Note 5]
Cooling method Forced air-cooled
Cooling fan noise (dBA)
73
76 78
Color RAL7016
EMC filter Built-in
Reactor [Note 6] External AC reactor (option)
Note 1: Capacity is calculated at 600V for the 575V class.
Note 2: Rated output current when the PWM carrier frequency (parameter ) is 2.5kHz.
⇒ Refer to 1.4.4 ”Current reduction curve” for details.
Note 3: An external power supply backup available (option) (Type: CPS002Z)
Note 4: ±10% when the inverter is used continuously (load of 100%).
Note 5: Inverters do not have wiring port covers. They have large openings, but there is no space to bend the
external cables inside the unit.
Note 6: AC reactor (option): Mandatory for VFAS1-6110KPC and above.