K-9
E6581528
11
[6] Speed/torque reference gain/bias setup [2/2] Sensorless vector/vector with sensor (●:Effective, -:Ineffective)
Default setting
Vector control
Title
Commun
ication
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
=
500V
-50Hz
=
575V
-60Hz
=
690V
-50Hz
Write
during
running
Speed
control
Torque
control
V/f
Constant
Reference
0212 RR/S4 input point 2 setting 0~100% 1/1 100 100 100 Enabled ●/● ●/● ● 7. 3. 1
0213 RR/S4 input point 2 frequency 0.0~ Hz 0.1/0.01 50.0 60.0 50.0 Enabled ●/● - ● 5. 11
0214 RR/S4 input point 1 rate 0~250% (for torque control etc.) 1/0.01 0 0 0 Enabled ●/● ●/● - *1
0215 RR/S4 input point 2 rate 0~250% (for torque control etc.) 1/0.01 100 100 100 Enabled ●/● ●/● - *1
0216 RX input point 1 setting -100~100% 1/1 0 0 0 Enabled ●/● ●/● ● 7. 3. 3
0217 RX input point 1 frequency 0.0~ Hz 0.1/0.01 0.0 0.0 0.0 Enabled ●/● - ● 7. 3. 3
0218 RX input point 2 setting -100~100% 1/1 100 100 100 Enabled ●/● ●/● ● 7. 3. 3
0219 RX input point 2 frequency 0.0~ Hz 0.1/0.01 50.0 60.0 50.0 Enabled ●/● - ● 7. 3. 3
0220 RX input point 1 rate -250~250% (for torque control etc.) 1/0.01 0 0 0 Enabled ●/● ●/● - *1
0221 RX input point 2 rate -250~250% (for torque control etc.) 1/0.01 100 100 100 Enabled ●/● ●/● - *1
0222 AI1 input point 1 setting -100~100% 1/1 0 0 0 Enabled ●/● ●/● ● *2
0223 AI1 input point 1 frequency 0.0~ Hz 0.1/0.01 0.0 0.0 0.0 Enabled ●/● - ● *2
0224 AI1 input point 2 setting -100-100% 1/1 100 100 100 Enabled ●/● ●/● ● *2
0225 AI1 input point 2 frequency 0.0~ Hz 0.1/0.01 50.0 60.0 50.0 Enabled ●/● - ● *2
0226 AI1 input point 1 rate -250~250% (for torque control etc.) 1/0.01 0 0 0 Enabled ●/● ●/● - *2
0227 AI1 input point 2 rate -250~250% (for torque control etc.)
1/
0.01
100 100 100 Enabled ●/● ●/● - *2
0228 AI2 input point 1 setting 0~100% 1/1 0 0 0 Enabled ●/● ●/● ● *2
0229 AI2 input point 1 frequency 0.0~ Hz 0.1/0.01 0.0 0.0 0.0 Enabled ●/● - ● *2
0230 AI2 input point 2 setting 0~100% 1/1 100 100 100 Enabled ●/● ●/● ● *2
0231 AI2 input point 2 frequency 0.0~ Hz 0.1/0.01 50.0 60.0 50.0 Enabled ●/● - ● *2
0234
RP/high speed pulse input
point 1 setting
0~100% 1/1 0 0 0 Enabled ●/● - ● *3
0235
RP/high speed pulse input
point 1 frequency
0.0~ Hz 0.1/0.01 0.0 0.0 0.0 Enabled ●/● - ● *3
0236
RP/high speed pulse input
point 2 setting
0~100% 1/1 100 100 100 Enabled ●/● - ● *3
0237
RP/high speed pulse input
point 2 frequency
0.0~ Hz 0.1/0.01 50.0 60.0 50.0 Enabled ●/● - ● *3
This parameter moves to a fundamental parameter.
*1: ⇒ For details, refer to Instruction Manual (E6581331) specified in Section 6.42.
*2: ⇒ For details, refer to Instruction Manual (E6581341) specified in Section 6.42.